Skip to main content
Siemens 3VA1132-3EF36-0JA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1132-3EF36-0JA0 SENTRON MCCB, 32 A, 3-Pole, Line

MPN3VA1132-3EF36-0JA0

Siemens SENTRON 3VA1132-3EF36-0JA0, Molded case circuit breaker, 3-pole, 32 A, line protection, TM240 overcurrent release, shunt trip, IP40 front.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VA1132-3EF36-0JA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA1132-3EF36-0JA0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C32 A
Current at 45 °C32 A
Current at 50 °C32 A
Current at 55 °C30.72 A
Current at 60 °C30.08 A
Current at 65 °C29.44 A
Current at 70 °C28.8 A
Switching capacity classN
Breaking capacity at 240 V75.6 kA
Breaking capacity at 415 V52.5 kA
Breaking capacity at 440 V32 kA
Breaking capacity at 690 V10.5 kA
3VA1132-3EF36-0JA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
3VA1132-3EF36-0JA0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1132-3EF36-0JA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA1132-3EF36-0JA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1132-3EF36-0JA0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

SENTRON 3VA1132-3EF36-0JA0 — 32 A MCCB with Shunt Trip

The interrupting ratings scale with system voltage: 75.6 kA at 240 V, 52.5 kA at 415 V, 32 kA at 440 V, and 10.5 kA at 690 V. At 415 V, that SCCR covers most industrial secondary-distribution fault levels without cascading upstream — a key selectivity consideration for panel builders coordinating downstream branch breakers. Current rating holds flat at 32 A up to 50 °C ambient, then derates to 30.72 A at 55 °C and 28.8 A at 70 °C.

The breaker carries an integrated auxiliary trip accessory (order code 3VA9688-0BL32) that ships as a factory-fitted component on this variant. If you are replacing a unit in the field, confirm the shunt trip coil voltage matches your control circuit — the base breaker does not include undervoltage release or auxiliary contacts.

The 3VA1132-3EF36-0JA0 measures 76.2 mm wide by 130 mm tall by 70 mm deep — a standard 3-pole MCCB footprint that fits Siemens SENTRON distribution panels and most DIN-rail-mount enclosures with the appropriate adapter.

Frequently asked questions

What is the interrupting rating of 3VA1132-3EF36-0JA0 at 415 V?

52.5 kA at 415 V, which covers most industrial secondary-distribution fault levels without requiring an upstream current-limiting fuse.

Does this MCCB include a shunt trip or undervoltage release?

It includes a shunt trip (STL) auxiliary release for remote voltage-triggered tripping, but does not include an undervoltage release or auxiliary contacts.

Where can I buy 3VA1132-3EF36-0JA0?

This part is sourced to order through independent distribution. Submit an RFQ for current availability and pricing — confirmed at quote time.

What is the ambient temperature derating for this breaker?

Rated 32 A continuous up to 50 °C, then derates to 30.72 A at 55 °C and 28.8 A at 70 °C. The full thermal curve is listed in the specs.

MPN
3VA1132-3EF36-0JA0