The TM110M thermal-magnetic overcurrent release gives it a fixed thermal curve paired with a magnetic trip, so you get motor-matched overload protection without an external relay. Breaking capacity runs 220 kA at 240 V, 154 kA at 415 V, and 121 kA at 440 V — numbers that tell you this breaker can interrupt very high fault currents at typical low-voltage distribution levels. At 500 V and 690 V it still holds 7.5 kA, which covers most industrial motor branch circuits on 480/600 V class systems.
Panel fit and thermal derating
Dimensions are 130 mm high, 76.2 mm wide, 70 mm deep — a compact 3-pole MCCB footprint that drops into standard SENTRON panel-mounting cutouts. Max power loss is 0.39 W, negligible for enclosure heat budgeting.