Skip to main content
Siemens 3VA1220-6EF32-0HA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1220-6EF32-0HA0 SENTRON MCCB, 200 A, 3-Pole, 220

MPN3VA1220-6EF32-0HA0

Siemens SENTRON 3VA1220-6EF32-0HA0, molded case circuit breaker, 3-pole, 200 A rated continuous current, line protection, 220 kA at 240 V, 70 mm depth, 105 mm width, 158 mm height.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VA1220-6EF32-0HA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA1220-6EF32-0HA0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C200 A
Current at 45 °C200 A
Current at 50 °C200 A
Current at 55 °C194 A
Current at 60 °C188 A
Current at 65 °C182 A
Current at 70 °C176 A
Switching capacity classH
Breaking capacity at 240 V220 kA
Breaking capacity at 415 V154 kA
Breaking capacity at 440 V36 kA
Breaking capacity at 690 V17 kA
3VA1220-6EF32-0HA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
3VA1220-6EF32-0HA0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1220-6EF32-0HA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA1220-6EF32-0HA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1220-6EF32-0HA0 — Mechanical
ParameterValue
Height158 mm
Width105 mm
Depth70 mm

Product details

MCCB for line protection — 200 A, 3-pole, high interrupting capacity

Its interrupting capacity reaches 220 kA at 240 V and 154 kA at 415 V, which means it can safely clear high-fault currents in a main feeder or distribution panel without cascading upstream — the sort of SCCR headroom a site electrical engineer needs for a 200 A bus.

Thermal derating and ambient temperature range

Above that, derating is linear: 194 A at 55 °C, 188 A at 60 °C, 182 A at 65 °C, and 176 A at 70 °C. If the panel ambient runs at 60 °C in a sealed enclosure, the effective continuous current drops to 188 A — that is the figure to use for the BOM line, not the 200 A nameplate.

Front protection is IP40. The 105 mm width is the standard 3-pole MCCB footprint for a 200 A frame in the SENTRON 3VA platform — it occupies one 105 mm-wide slot in a distribution panel. No auxiliary contact or communication module adds depth beyond the 70 mm listed.

Frequently asked questions

Where can I buy 3VA1220-6EF32-0HA0 and how do I get a price?

This part is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

What are the key ratings for 3VA1220-6EF32-0HA0?

It is a 3-pole molded case circuit breaker rated 200 A continuous current (Iu) with a TM240 thermal-magnetic release. Interrupting capacity is 220 kA at 240 V, 154 kA at 415 V, 36 kA at 440 V, and 17 kA at 690 V. The rated insulation voltage Ui is 800 V.

What is the depth of 3VA1220-6EF32-0HA0?

The depth is 70 mm. Width is 105 mm and height is 158 mm.

What compliance documentation does Siemens provide for this MCCB?

The evidence does not list specific compliance documents (RoHS, REACH, UL, IEC) for this order code. The reference code per DIN EN 81346-2 is Q. For full compliance documentation, request it with the RFQ.

MPN