Skip to main content
Siemens 3VA1450-4EE32-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1450-4EE32-0AA0 SENTRON MCCB, 500 A, 3-Pole, TM22

MPN3VA1450-4EE32-0AA0

Siemens SENTRON 3VA1450-4EE32-0AA0, molded case circuit breaker, 3-pole, 500 A, TM220 thermal-magnetic release, line protection version.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3VA1450-4EE32-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA1450-4EE32-0AA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C500 A
Current at 45 °C500 A
Current at 50 °C500 A
Current at 55 °C488 A
Current at 60 °C476 A
Current at 65 °C464 A
Current at 70 °C452 A
Switching capacity classS
Breaking capacity at 240 V121 kA
Breaking capacity at 415 V75.6 kA
Breaking capacity at 440 V75.6 kA
Breaking capacity at 500 V52.5 kA
Breaking capacity at 690 V11.9 kA
Power loss, max.122.7 W
3VA1450-4EE32-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM220
Overcurrent protection functionLI
Ground-fault monitoringWithout
3VA1450-4EE32-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1450-4EE32-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA1450-4EE32-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1450-4EE32-0AA0 — Mechanical
ParameterValue
Height248 mm
Width138 mm
Depth110 mm
Height (in)9.76 in
Width (in)5.43 in
Depth (in)4.33 in

Product details

Siemens 3VA1450-4EE32-0AA0 — 500 A SENTRON MCCB, TM220 Release

The Siemens 3VA1450-4EE32-0AA0 is a 3-pole SENTRON molded case circuit breaker rated for a continuous current Iu of 500 A at ambient temperatures up to 50 °C, with no derating needed at 40 °C, 45 °C, or 50 °C. Above that, the current rating steps down to 488 A at 55 °C, 476 A at 60 °C, 464 A at 65 °C, and 452 A at 70 °C — useful to know if this breaker sits in a warm enclosure or near other heat sources. Breaking capacity runs 121 kA at 240 V, 75.6 kA at both 415 V and 440 V, 52.5 kA at 500 V, and 11.9 kA at 690 V. It carries a TM220 thermal-magnetic overcurrent release — that's a fixed, non-adjustable thermal trip with a magnetic short-circuit pickup set at the factory. It's a straight line-protection breaker: no bells, no auxiliary electronics.

Frequently asked questions

What is the breaking capacity of 3VA1450-4EE32-0AA0 at 415 V?

75.6 kA at 415 V, and the same rating applies at 440 V. At 240 V it's 121 kA, at 500 V it's 52.5 kA, and at 690 V it's 11.9 kA.

What does the TM220 release designation mean on this MCCB?

TM220 means a thermal-magnetic overcurrent release with a fixed thermal trip and a fixed magnetic short-circuit pickup — no field adjustment of the trip curve. It's a line-protection breaker, not a motor-protection or adjustable-trip device.

Where can I buy 3VA1450-4EE32-0AA0 and get current pricing?

Submit an RFQ through this listing. We source through independent distribution and confirm availability and current pricing at quote time — no stock count or price figure is published here.

MPN
3VA1450-4EE32-0AA0