Skip to main content
Siemens 3VA1463-6FF42-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1463-6FF42-0AA0 SENTRON MCCB, 315 A, 220 kA

MPN3VA1463-6FF42-0AA0
Active

Siemens SENTRON 3VA1463-6FF42-0AA0, molded case circuit breaker, 315 A, 4-pole, TM240 overcurrent release, 220 kA interrupting at 240 V, IP40 front, 184 x 248 x 110 mm.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VA1463-6FF42-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
3VA1463-6FF42-0AA0 — Ratings
ParameterValue
Number of poles4
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C630 A
Current at 45 °C630 A
Current at 50 °C630 A
Current at 55 °C618 A
Current at 60 °C607 A
Current at 65 °C595 A
Current at 70 °C583 A
Switching capacity classH
Breaking capacity at 240 V220 kA
Breaking capacity at 415 V154 kA
Breaking capacity at 440 V154 kA
Breaking capacity at 500 V121 kA
Breaking capacity at 690 V17 kA
Power loss, max.192.9 W
3VA1463-6FF42-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA1463-6FF42-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1463-6FF42-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA1463-6FF42-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1463-6FF42-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height248 mm
Width184 mm
Depth110 mm
Height (in)9.76 in
Width (in)7.24 in
Depth (in)4.33 in

Product details

Its TM240 thermal-magnetic overcurrent release handles both overload and short-circuit conditions without external trip units. The interrupting capacity hits 220 kA at 240 V AC, dropping to 154 kA at 415 V and 440 V, 121 kA at 500 V, and 17 kA at 690 V — so at 480 V typical of North American industrial panels you're looking at the 121 kA curve. That's a serious fault-clearing number; it keeps downstream gear safe on high-available-fault buswork.

Full 630 A rating holds from 40 °C to 50 °C ambient; above that it steps down — 618 A at 55 °C, 607 A at 60 °C, 595 A at 65 °C, 583 A at 70 °C. That's a gentle slope, so a warm enclosure doesn't gut the breaker. The 184 mm width, 248 mm height, and 110 mm depth (7.24 x 9.76 x 4.33 inches) mean it fits standard MCCB mounting footprints; the IP40 front keeps dust out of the panel face but isn't rated for washdown environments.

Frequently asked questions

Where can I buy 3VA1463-6FF42-0AA0 and how do I get a price?

This part is sourced and quoted to order against an RFQ through independent distribution channels. Submit a request for quote (RFQ) to confirm current availability and pricing at the time of your order.

What are the key ratings for 3VA1463-6FF42-0AA0?

Rated 315 A continuous, 4-pole, with a TM240 thermal-magnetic release. Interrupting capacity is 220 kA at 240 V, 154 kA at 415 V and 440 V, 121 kA at 500 V, and 17 kA at 690 V. Full 630 A rating holds up to 50 °C ambient, then derates to 583 A at 70 °C.

What is 3VA1463-6FF42-0AA0's listed depth?

Depth is 110 mm (4.33 inches). Width is 184 mm (7.24 inches), height is 248 mm (9.76 inches).

MPN