Skip to main content
Siemens 3VA2040-5JP32-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens SENTRON 3VA2040-5JP32-0AA0 MCCB, 40 A, 3-Pole, 187 k

MPN3VA2040-5JP32-0AA0
Active

Siemens SENTRON 3VA2040-5JP32-0AA0, 3-pole molded case circuit breaker, 40 A continuous, ETU550 trip unit, 187 kA at 240 V, IP40 front.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VA2040-5JP32-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
3VA2040-5JP32-0AA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C40 A
Current at 45 °C40 A
Current at 50 °C40 A
Current at 55 °C40 A
Current at 60 °C40 A
Current at 65 °C40 A
Current at 70 °C40 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V75.6 kA
Breaking capacity at 690 V3 kA
Power loss, max.2.2 W
3VA2040-5JP32-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU550
Overcurrent protection functionLSI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA2040-5JP32-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typeon both sides nut keeper kit
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2040-5JP32-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionYes
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA2040-5JP32-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2040-5JP32-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.25 000
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.13 in
Width (in)4.13 in
Depth (in)3.39 in

Product details

MCCB for line protection with ETU550 trip unit

The Siemens SENTRON 3VA2040-5JP32-0AA0 is a 3-pole molded case circuit breaker (MCCB) rated for 40 A continuous current across the full ambient range from 40 °C to 70 °C — no derating needed up to that ceiling. It's designed for line protection duty, meaning it sits on the feeder side of a distribution panel, not as a motor starter.

Breaking capacity across voltage levels

This MCCB delivers 187 kA at 240 V, 121 kA at 415 V and 440 V, 75.6 kA at 500 V, and 3 kA at 690 V.

Electrical ratings and insulation

Power loss is 2.2 W maximum — negligible for panel thermal calculations but worth noting if you're packing multiple breakers in a sealed enclosure. No undervoltage release or trip indicator is fitted on this variant, so if you need remote shunt-trip capability, confirm the accessory slot compatibility.

Frequently asked questions

What is the physical size of 3VA2040-5JP32-0AA0?

105 mm wide, 181 mm tall, 86 mm deep.

MPN