Motor protection MCCB with 200 kA interrupting capacity
The continuous current rating In is 25 A, with overload protection Ir adjustable from 10 A to 25 A and short-circuit protection Isd adjustable 3…15×Ir. Instantaneous pickup Ii is fixed at 15×In. This is a class E breaking capacity device rated Icu = 200 kA at 415 V AC — meaning it can safely interrupt a fault current up to 200,000 A without damage, which is the highest standard interrupting rating in the 3VA2 family for this frame size. That level of SCCR headroom is typically specified for large industrial switchboards with high available fault current, or for selective coordination downstream of a transformer.
Active production, made-to-order lead time
Note the product class is C: products manufactured or produced to order, which cannot be reused or returned against credit. This means the unit is built per order rather than stocked as a shelf item, so lead time is driven by the production schedule.
Compliance and regulatory documentation
RoHS compliance effective since 01-10-19. The part contains lead (CAS 7439-92-1) above the 0.1% threshold per the REACH candidate list, requiring Article 33 duty-to-inform for downstream users. Export Control Regulations are AL: N / ECCN: 9N9999, meaning no special export license is required for most destinations. The product family is the 3VA Molded Case Circuit Breakers up to 1600 A, IEC.
Panel integration and connection
Packaged singly, dimensions 200.00 × 134.00 × 145.00 mm. Terminal connection type per the description — verify lug size against your cable cross-section during panel layout. The 3-pole form factor mounts in the standard MCCB footprint; allow clearance for arc flash and access to the ETU350M adjustment dials on the front face.