That's the kind of fault-current headroom that lets you use this breaker downstream of a large transformer or a high-capacity bus without worrying about cascading failure.
The 25 A continuous rating holds flat across the full ambient range — 25 A at 40 °C, 45 °C, all the way up to 70 °C. No derating curve to chase; that's a solid spec for a warm panel or a high-ambient machine cell. Line protection design, no ground-fault monitoring, no undervoltage release fitted. Insulation voltage rated 800 V, operating voltage up to 690 V AC.
Panel integration
That's a 3-pole frame that bolts into the SENTRON 3VA base plate or DIN-rail adapter.