The Siemens 3VA2163-6JP36-0AA0 is a 3-pole SENTRON molded case circuit breaker rated for 63 A continuous current across the full ambient range from 40 °C to 70 °C — no derating needed up to that ceiling. That flat thermal curve simplifies panel design: you size the bus and cable for 63 A and the breaker holds it, even in a warm enclosure. Interrupting capacity is the headline: 242 kA at 240 V, 187 kA at 415 V and 440 V, 121 kA at 500 V, and 3.7 kA at 690 V. At the common 415 V distribution level, 187 kA SCCR means this breaker can clear a bolted fault on a large transformer secondary without rupturing — it's sized for high-fault industrial switchboards, not light commercial panels. The ETU550 electronic trip unit gives adjustable long-time, short-time, instantaneous, and ground-fault protection curves. Communication function is built in, so the breaker can report status and trip events over the plant network — useful for a maintenance team tracking nuisance trips on a bottling line or a packaging cell.
Siemens 3VA2163-6JP36-0AA0 SENTRON MCCB, 63 A, 242 kA at 240
MPN3VA2163-6JP36-0AA0
Active
Siemens SENTRON 3VA2163-6JP36-0AA0, molded case circuit breaker, 3-pole, 63 A continuous, ETU550 electronic trip, 242 kA at 240 V, 187 kA at 415 V, communication function, IP40 front.
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026
Specifications
| Parameter | Value |
|---|---|
| Product designation | Molded case circuit breaker |
| Brand / range | SENTRON |
| Parameter | Value |
|---|---|
| Number of poles | 3 |
| Rated operational voltage Ue (AC) | 690 V |
| Rated insulation voltage Ui | 800 V |
| Current at 40 °C | 63 A |
| Current at 45 °C | 63 A |
| Current at 50 °C | 63 A |
| Current at 55 °C | 63 A |
| Current at 60 °C | 63 A |
| Current at 65 °C | 63 A |
| Current at 70 °C | 63 A |
| Switching capacity class | H |
| Breaking capacity at 240 V | 242 kA |
| Breaking capacity at 415 V | 187 kA |
| Breaking capacity at 440 V | 187 kA |
| Breaking capacity at 500 V | 121 kA |
| Breaking capacity at 690 V | 3.7 kA |
| Power loss, max. | 4 W |
| Parameter | Value |
|---|---|
| Overcurrent release (trip unit) type | ETU550 |
| Overcurrent protection function | LSI |
| Ground-fault monitoring | Without |
| Grounding protection function | No |
| Parameter | Value |
|---|---|
| Main circuit connection type | double-sided box terminal |
| Main circuit connector arrangement | Front terminal |
| Protection class (IP), front | IP40 |
| Parameter | Value |
|---|---|
| Undervoltage release | No |
| Voltage trigger | No |
| Trip indicator | No |
| Communication function | Yes |
| Measurement function | No |
| Motor drive option | Yes |
| Auxiliary CO contacts | 0 |
| Parameter | Value |
|---|---|
| Operating temperature, max. | 70 °C |
| Operating temperature, min. | -25 °C |
| Storage temperature, max. | 80 °C |
| Storage temperature, min. | -40 °C |
| Parameter | Value |
|---|---|
| Mechanical service life (operating cycles), typ. | 25 000 |
| Height | 181 mm |
| Width | 105 mm |
| Depth | 86 mm |
| Height (in) | 7.13 in |
| Width (in) | 4.13 in |
| Depth (in) | 3.39 in |
Product details
Frequently asked questions
How do I get current pricing and availability for 3VA2163-6JP36-0AA0?
Submit an RFQ through this listing. The part is sourced and quoted to order through independent distribution; availability and current pricing are confirmed at quote time.
What is the interrupting capacity of 3VA2163-6JP36-0AA0 at 415 V?
187 kA at 415 V. The same rating applies at 440 V. At 240 V it reaches 242 kA.
Does 3VA2163-6JP36-0AA0 have communication capability?
Yes, the communication function is built in. It can report status and trip events over the plant network.
MPN
3VA2163-6JP36-0AA0