Siemens SENTRON 3VA2163-8KP32-0AA0 — 63 A MCCB with ETU850 Trip Unit
It carries an ETU850 electronic overcurrent release, giving you adjustable trip curves and communication capability for integration with higher-level control systems — a step up from fixed thermal-magnetic breakers when you need selectivity coordination or remote monitoring. Breaking capacity runs 440 kA at 240 V, 330 kA at 415 V and 440 V, 220 kA at 500 V, and 52.5 kA at 690 V — figures that cover most industrial service-entrance and distribution applications without needing a current-limiting fuse upstream.
Rated insulation voltage 800 V, power loss 3.1 W maximum, operating temperature range -25 °C to 70 °C, storage range -40 °C to 80 °C.