Breaking capacity and derating
Breaking capacity hits 187 kA at 240 V, drops to 121 kA at 415 V and 440 V, then 79 kA at 500 V, and 4.25 kA at 690 V. The 4.25 kA at 690 V still covers most motor branch circuits at that voltage.
Rated 63 A from 40 °C through 50 °C ambient; above that it derates linearly to 53.55 A at 70 °C.