Skip to main content
Siemens 3VA4110-4ED34-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA4110-4ED34-0AA0 SENTRON MCCB, 100 A, 65 kA at 240

MPN3VA4110-4ED34-0AA0
Active

Siemens SENTRON molded-case circuit breaker, 3VA4110-4ED34-0AA0, 3-pole, 100 A at 40 °C, TM210 thermal-magnetic release, 65 kA at 240 V AC, IP40 front.

$132.08Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VA4110-4ED34-0AA0 — Identification
ParameterValue
Product designationMolded-case circuit breaker
Brand / rangeSENTRON
3VA4110-4ED34-0AA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Current at 40 °C100 A
Current at 45 °C98 A
Current at 50 °C96 A
Current at 55 °C93 A
Current at 60 °C91 A
Current at 65 °C89 A
Current at 70 °C87 A
Switching capacity classS
Breaking capacity at 240 V65 kA
Power loss, max.22.8 W
3VA4110-4ED34-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA4110-4ED34-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typeInfeed side: Low tab
Main circuit connector arrangementoutput side: circular conductor connection
Protection class (IP), frontIP40
3VA4110-4ED34-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts0
3VA4110-4ED34-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA4110-4ED34-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.15 000
Height129.4 mm
Width76.2 mm
Depth75.1 mm
Height (in)5.09 in
Width (in)3 in
Depth (in)2.96 in

Product details

The Siemens 3VA4110-4ED34-0AA0 is a 3-pole SENTRON molded-case circuit breaker (MCCB) rated 100 A at 40 °C, with a TM210 thermal-magnetic release for system protection in distribution panels and motor control centers. Its interrupting capacity hits 65 kA at 240 V AC and 25 kA at 480 V AC — that's SCCR headroom for most industrial feeders and downstream coordination without cascading upstream. Rated operating voltage goes to 690 V AC, and the breaker handles ambient temperatures from -25 °C to 70 °C, with a 22.8 W max power loss at full load.

The 100 A rating at 40 °C is the continuous current you can push through it in a typical 40 °C panel ambient. Derate to 87 A at 70 °C if the enclosure runs hot — the thermal curve matters for real-world loading. 65 kA at 240 V means it safely interrupts a fault up to that level without blowing apart or welding contacts, so you can place it near high-capacity transformers or upstream of smaller branch breakers. No adjustable trip unit, no ground-fault module, no communication. It's a straight system-protection breaker for fixed-load feeders.

The breaker measures 76.2 mm wide, 129.4 mm tall, and 75.1 mm deep.

Frequently asked questions

Does this MCCB have an adjustable trip unit or ground-fault protection?

No. The TM210 release is a fixed thermal-magnetic trip — no adjustable settings, no ground-fault monitoring, and no communication module. It's a straight system-protection breaker.

MPN
3VA4110-4ED34-0AA0