Skip to main content
Siemens 3VA4110-5ED14-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA4110-5ED14-0AA0 SENTRON MCCB, 1-pole, 100 A, 85 k

MPN3VA4110-5ED14-0AA0
Active

Siemens SENTRON 3VA4110-5ED14-0AA0, 1-pole molded-case circuit breaker, 100 A at 40 °C, TM210 thermal-magnetic release, 85 kA at 120 V interrupting capacity, IP40 front protection.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VA4110-5ED14-0AA0 — Identification
ParameterValue
Product designationMolded-case circuit breaker
Brand / rangeSENTRON
3VA4110-5ED14-0AA0 — Ratings
ParameterValue
Number of poles1
Rated operational voltage Ue (AC)415 V
Current at 40 °C100 A
Current at 45 °C98 A
Current at 50 °C96 A
Current at 55 °C93 A
Current at 60 °C91 A
Current at 65 °C89 A
Current at 70 °C87 A
Switching capacity classM
Power loss, max.7.6 W
3VA4110-5ED14-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA4110-5ED14-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typeInfeed side: Low tab
Protection class (IP), frontIP40
3VA4110-5ED14-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts0
3VA4110-5ED14-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA4110-5ED14-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.15 000
Height129.4 mm
Width25.4 mm
Depth75.1 mm
Height (in)5.09 in
Width (in)1 in
Depth (in)2.96 in

Product details

The Siemens 3VA4110-5ED14-0AA0 is a 1-pole SENTRON molded-case circuit breaker (MCCB) rated 100 A continuous at 40 °C ambient, with a TM210 thermal-magnetic release. The interrupting capacity is 85 kA at 120 V AC, 35 kA at 277 V, and 18 kA at 347 V; at 415 V operating voltage the breaker still clears high-fault scenarios common in industrial distribution. The single-pole footprint is 25.4 mm wide — one standard DIN module — so it slots into a panel without eating extra rail space.

What it does not carry

This is a straight system-protection MCCB — overload and short-circuit only. If the BOM calls for shunt trip or remote signaling, this is not that variant.

Frequently asked questions

What is 3VA4110-5ED14-0AA0's listed depth?

75.1 mm. That is the body depth from the DIN-rail mounting surface to the front of the breaker.

MPN
3VA4110-5ED14-0AA0