Skip to main content
Siemens 3VA4120-4ED34-1AA0 — Molded Case Circuit Breakers (MCCB)

Siemens SENTRON 3VA4120-4ED34-1AA0 MCCB, 20 A, 3-Pole, 65 kA

MPN3VA4120-4ED34-1AA0
Active

Siemens SENTRON, molded-case circuit breaker, 3VA4120-4ED34-1AA0, 3-pole, 20 A rated current, 65 kA at 240 V, 25 kA at 480 V, TM210 release.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VA4120-4ED34-1AA0 — Identification
ParameterValue
Product designationMolded-case circuit breaker
Brand / rangeSENTRON
Product versionSystem protection
3VA4120-4ED34-1AA0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C20 A
Current at 45 °C20 A
Current at 50 °C20 A
Current at 55 °C20 A
Current at 60 °C19 A
Current at 65 °C19 A
Current at 70 °C18 A
Switching capacity classS
Breaking capacity at 240 V65 kA
Power loss, max.8.5 W
3VA4120-4ED34-1AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout
3VA4120-4ED34-1AA0 — Construction & Connection
ParameterValue
Main circuit connection typeInfeed side: Low tab
Main circuit connector arrangementLoad side: Circular conductor terminal
Protection class (IP), frontIP40
3VA4120-4ED34-1AA0 — Accessories & Functions
ParameterValue
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts0
3VA4120-4ED34-1AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA4120-4ED34-1AA0 — Mechanical
ParameterValue
Height129.4 mm
Width76.2 mm
Depth75.1 mm
Height (in)5.1 in
Width (in)3 in
Depth (in)3 in

Product details

Siemens SENTRON 3VA4120-4ED34-1AA0 — 20 A MCCB, 3-Pole, 65 kA at 240 V

The Siemens SENTRON 3VA4120-4ED34-1AA0 is a 3-pole molded-case circuit breaker (MCCB) rated for a continuous current of 20 A at 40 °C, with a thermal-magnetic TM210 release that is fixed at 300 A instantaneous trip (li min. and max. both 300 A).

At 240 V it clears 65 kA — that is the high-fault rating that makes this breaker suitable for main or large-feeder positions in a 240 VAC panelboard. At 480 V the rating drops to 25 kA, and at 600 Y/347 V it is 14 kA, so the application voltage directly governs where this MCCB can be placed without exceeding its interrupting capacity.

Rated 20 A from 40 °C through 55 °C; at 60 °C and 65 °C it holds 19 A, and at 70 °C it derates to 18 A. The TM210 release is thermal-magnetic — no electronic adjustment — so the fixed li setting at 300 A means the magnetic trip is not field-adjustable. Dimensions are 76.2 mm wide (3 in), 129.4 mm tall, 75.1 mm deep, fitting a standard 3-pole MCCB footprint on DIN rail or panel-mount.

Frequently asked questions

What is 3VA4120-4ED34-1AA0's interrupting rating at 480 V?

25 kA at 480 V, and 14 kA at 600 Y/347 V.

Where can I buy 3VA4120-4ED34-1AA0 and how is it quoted?

Sourced and quoted to order against an RFQ through independent distribution; availability and current pricing confirmed at quote time.

MPN
3VA4120-4ED34-1AA0