Skip to main content
Siemens 3VA4120-6ED14-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens SENTRON 3VA4120-6ED14-0AA0 MCCB, 1-Pole, 20 A, TM210

MPN3VA4120-6ED14-0AA0
Active

Siemens SENTRON 3VA4120-6ED14-0AA0, 1-pole molded-case circuit breaker, system protection design, TM210 thermal-magnetic release, rated 20 A at 40 °C, interrupting capacity 150 kA at 120 V AC, 75.1 mm depth, IP40 front protection.

$64.77Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VA4120-6ED14-0AA0 — Identification
ParameterValue
Product designationMolded-case circuit breaker
Brand / rangeSENTRON
3VA4120-6ED14-0AA0 — Ratings
ParameterValue
Number of poles1
Rated operational voltage Ue (AC)415 V
Current at 40 °C20 A
Current at 45 °C20 A
Current at 50 °C19 A
Current at 55 °C19 A
Current at 60 °C18 A
Current at 65 °C18 A
Current at 70 °C17 A
Switching capacity classH
Power loss, max.2.8 W
3VA4120-6ED14-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA4120-6ED14-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typeInfeed side: Low tab
Protection class (IP), frontIP40
3VA4120-6ED14-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts0
3VA4120-6ED14-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA4120-6ED14-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.15 000
Height129.4 mm
Width25.4 mm
Depth75.1 mm
Height (in)5.09 in
Width (in)1 in
Depth (in)2.96 in

Product details

The 3VA4120-6ED14-0AA0: At 25.4 mm wide (1 inch) and 75.1 mm deep, this breaker occupies a single-pole slot in a SENTRON panelboard or similar DIN-rail assembly, provided the bus or line-side lugs match the 415 V AC rated voltage. The IP40 front protection means it resists tool entry from the front but is not sealed against washdown — fit it in a dry enclosure or behind a gland plate.

Frequently asked questions

What is the interrupting capacity of 3VA4120-6ED14-0AA0 at 120 V?

It is rated 150 kA at 120 V AC, which is very high for a 1-pole breaker — sufficient to clear faults in high-capacity transformer-fed panels without cascading.

What is the continuous current rating of this MCCB at elevated temperatures?

At 40 °C it carries 20 A. Derating is linear: 19 A at 50 °C, 18 A at 60 °C, and 17 A at 70 °C. The thermal-magnetic TM210 release governs the trip curve.

Where can I buy 3VA4120-6ED14-0AA0?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time; no stock count or lead-time figure is published here.

MPN
3VA4120-6ED14-0AA0