Skip to main content
Siemens 3VM1110-4ED12-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VM1110-4ED12-0AA0 SENTRON MCCB, 1-pole, 100 A, 76 k

MPN3VM1110-4ED12-0AA0
Active

Siemens SENTRON 3VM1110-4ED12-0AA0, 1-pole molded case circuit breaker, line protection, 100 A (40-50 °C), 76 kA at 240 V AC, TM210 release, switching capacity class S.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VM1110-4ED12-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VM1110-4ED12-0AA0 — Ratings
ParameterValue
Number of poles1
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C98 A
Current at 60 °C96 A
Current at 65 °C94 A
Current at 70 °C91 A
Switching capacity classS
Breaking capacity at 240 V76 kA
Breaking capacity at 415 V9 kA
Power loss, max.8 W
3VM1110-4ED12-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout
3VM1110-4ED12-0AA0 — Construction & Connection
ParameterValue
Main circuit connector arrangementFront connection
Protection class (IP), frontIP40
3VM1110-4ED12-0AA0 — Accessories & Functions
ParameterValue
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts0
3VM1110-4ED12-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VM1110-4ED12-0AA0 — Mechanical
ParameterValue
Height130 mm
Width25.4 mm
Depth70 mm
Height (in)5.1 in
Width (in)1 in
Depth (in)2.8 in

Product details

It carries 100 A continuously from 40 °C through 50 °C without derating — at 55 °C it still holds 98 A, and at 70 °C it delivers 91 A. The 9 kA at 415 V covers standard European distribution panels. It uses a TM210 thermal-magnetic overcurrent release with adjustable short-circuit pickup up to 1 000 A. The release type LI (long-time and instantaneous) means no electronic trip unit — simpler, more robust in dirty power environments, and easier for a field tech to troubleshoot.

The 25.4 mm width (1 inch) is a single pole pitch — standard for 1-pole MCCBs on a DIN rail. The 70 mm depth and 130 mm height mean it fits a standard distribution board without overhang. IP40 on the front is fine for indoor panelboards; not rated for washdown.

What the switching capacity class S means

The switching capacity class S is the standard-performance tier in the SENTRON 3VM range.

Frequently asked questions

What overcurrent release does this breaker use?

It uses a TM210 thermal-magnetic release with LI protection (long-time and instantaneous), adjustable short-circuit pickup up to 1 000 A.

MPN
3VM1110-4ED12-0AA0