Siemens 3VM1163-4EE42-0AA0 SENTRON MCCB, 63A 4-Pole, 121kA a

MPN3VM1163-4EE42-0AA0
Active

Siemens SENTRON 3VM1163-4EE42-0AA0, 4-pole molded case circuit breaker, 63 A, 121 kA at 240 V AC, TM220 release, IP40 front.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VM1163-4EE42-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VM1163-4EE42-0AA0 — Ratings
ParameterValue
Number of poles4
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C62 A
Current at 60 °C61 A
Current at 65 °C60 A
Current at 70 °C58 A
Switching capacity classS
Breaking capacity at 240 V121 kA
Breaking capacity at 415 V76 kA
Breaking capacity at 440 V53 kA
Breaking capacity at 500 V12 kA
Power loss, max.17 W
3VM1163-4EE42-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM220
Overcurrent protection functionLI
Ground-fault monitoringWithout
3VM1163-4EE42-0AA0 — Construction & Connection
ParameterValue
Main circuit connector arrangementFront connection
Protection class (IP), frontIP40
3VM1163-4EE42-0AA0 — Accessories & Functions
ParameterValue
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts0
3VM1163-4EE42-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VM1163-4EE42-0AA0 — Mechanical
ParameterValue
Height130 mm
Width101.6 mm
Depth70 mm
Height (in)5.1 in
Width (in)4 in
Depth (in)2.8 in

Product details

The Siemens SENTRON 3VM1163-4EE42-0AA0 is a 4-pole molded case circuit breaker (MCCB) rated for line protection, carrying a continuous current of 63 A at 40 °C through 50 °C, with a slight thermal derating above that — 62 A at 55 °C, 61 A at 60 °C, 60 A at 65 °C, and 58 A at 70 °C. The interrupting capacity hits 121 kA at 240 V AC, 76 kA at 415 V, 53 kA at 440 V, and 12 kA at 500 V — numbers that matter for high-fault service entrances or large motor branch circuits where the available fault current is substantial. The TM220 thermal-magnetic release gives you an adjustable long-time pickup up to 630 A, so this breaker can be tuned to the load without swapping out the whole unit.

IP40 on the front keeps finger-sized objects out but isn't sealed against washdown — it's fine inside a dry enclosure, not out in the weather.

Frequently asked questions

Where can I buy 3VM1163-4EE42-0AA0?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is the breaking capacity of this breaker at 240 V?

The interrupting capacity is 121 kA at 240 V AC, which covers high-fault service entrances and large motor branch circuits.

Will 3VM1163-4EE42-0AA0 drop into a panel specified around 3VA1010-2ED32-0AD0 without rewiring?

The 3VM1163-4EE42-0AA0 is a 4-pole MCCB with a 63 A frame and TM220 release, while the 3VA1010-2ED32-0AD0 is a different frame size and release type. Panel fit depends on the specific mounting footprint and bus arrangement — verify the physical dimensions and terminal spacing before assuming a direct drop-in.

MPN
3VM1163-4EE42-0AA0