Siemens 3VM1163-4ED22-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VM1163-4ED22-0AA0 SENTRON MCCB, 63 A, 76 kA at 415

MPN3VM1163-4ED22-0AA0
Active

Siemens SENTRON 3VM1 series, molded case circuit breaker, 2-pole, 63 A (40-50 °C), 76 kA at 415 V AC, TM210 thermal-magnetic release, IP40 front.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VM1163-4ED22-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection

Ratings

3VM1163-4ED22-0AA0 — Ratings
ParameterValue
Number of poles2
Rated operational voltage Ue (AC)415 V
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C62 A
Current at 60 °C61 A
Current at 65 °C60 A
Current at 70 °C58 A
Switching capacity classS
Breaking capacity at 240 V121 kA
Breaking capacity at 415 V76 kA
Power loss, max.12 W

Protection & Trip Unit

3VM1163-4ED22-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout

Construction & Connection

3VM1163-4ED22-0AA0 — Construction & Connection
ParameterValue
Main circuit connector arrangementFront connection
Protection class (IP), frontIP40

Accessories & Functions

3VM1163-4ED22-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts0

Environmental

3VM1163-4ED22-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VM1163-4ED22-0AA0 — Mechanical
ParameterValue
Height130 mm
Width50.8 mm
Depth70 mm
Height (in)5.12 in
Width (in)2 in
Depth (in)2.76 in

Product details

SENTRON 3VM1 — 63 A MCCB for line protection

The Siemens 3VM1163-4ED22-0AA0 is a 2-pole SENTRON molded case circuit breaker (MCCB) for line protection. It carries a 63 A rating sustained from 40 °C through 50 °C, then derates to 58 A at 70 °C — the full thermal curve is in the spec table so you can size for a warm panel without guesswork. Breaking capacity is 121 kA at 240 V AC and 76 kA at 415 V AC — those figures cover most North American and European distribution fault levels without needing a current-limiting upstream device. The TM210 thermal-magnetic release has an adjustable li of 630 A max, giving coordination headroom for motor feeders or transformer inrush. Front protection is IP40, so it handles incidental tool contact in a closed panel but not washdown. Rated insulation voltage is 500 V, and DC operation is supported up to 250 V — useful for battery or UPS circuits.

Lifecycle and sourcing

Operating temperature range is -25 °C to 70 °C, storage from -40 °C to 80 °C. Maximum power loss is 12 W — negligible for panel thermal budgeting but worth noting if you are packing multiple breakers in a sealed enclosure.

Physical fit and panel integration

Dimensions are 70 mm deep, 50.8 mm wide, 130 mm tall — a standard 2-pole MCCB footprint that drops into most DIN-rail or bolt-on panel layouts without re-drilling. The 50.8 mm width matches the common 2-inch per-pole spacing used across SENTRON 3VM1 and 3VA families.

Frequently asked questions

Where can I buy 3VM1163-4ED22-0AA0 and how is it quoted?

It is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at the time of quote — submit an RFQ for a firm price and lead time.

What is the breaking capacity of this MCCB at different voltages?

At 240 V AC it interrupts 121 kA; at 415 V AC it interrupts 76 kA. The rated operational voltage is 415 V AC, with DC operation supported up to 250 V.

What are the physical dimensions of 3VM1163-4ED22-0AA0?

Depth is 70 mm, width is 50.8 mm, height is 130 mm — a standard 2-pole MCCB footprint that fits existing SENTRON panel layouts.

What type of overcurrent release does this breaker use?

It uses a TM210 thermal-magnetic release with an adjustable instantaneous trip current (li) up to 630 A.

MPN
3VM1163-4ED22-0AA0