Siemens 3VM1163-4ED22-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VM1163-4ED22-0AA0 SENTRON MCCB, 63 A, 76 kA at 415

MPN3VM1163-4ED22-0AA0
Active

Siemens SENTRON 3VM1 series, molded case circuit breaker, 2-pole, 63 A (40-50 °C), 76 kA at 415 V AC, TM210 thermal-magnetic release, IP40 front.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VM1163-4ED22-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VM1163-4ED22-0AA0 — Ratings
ParameterValue
Number of poles2
Rated operational voltage Ue (AC)415 V
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C62 A
Current at 60 °C61 A
Current at 65 °C60 A
Current at 70 °C58 A
Switching capacity classS
Breaking capacity at 240 V121 kA
Breaking capacity at 415 V76 kA
Power loss, max.12 W
3VM1163-4ED22-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout
3VM1163-4ED22-0AA0 — Construction & Connection
ParameterValue
Main circuit connector arrangementFront connection
Protection class (IP), frontIP40
3VM1163-4ED22-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts0
3VM1163-4ED22-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VM1163-4ED22-0AA0 — Mechanical
ParameterValue
Height130 mm
Width50.8 mm
Depth70 mm
Height (in)5.12 in
Width (in)2 in
Depth (in)2.76 in

Product details

It carries a 63 A rating sustained from 40 °C through 50 °C, then derates to 58 A at 70 °C — the full thermal curve is in the spec table so you can size for a warm panel without guesswork. The TM210 thermal-magnetic release has an adjustable li of 630 A max, giving coordination headroom for motor feeders or transformer inrush.

Dimensions are 70 mm deep, 50.8 mm wide, 130 mm tall — a standard 2-pole MCCB footprint that drops into most DIN-rail or bolt-on panel layouts without re-drilling. The 50.8 mm width matches the common 2-inch per-pole spacing used across SENTRON 3VM1 and 3VA families.

Frequently asked questions

Where can I buy 3VM1163-4ED22-0AA0 and how is it quoted?

It is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at the time of quote — submit an RFQ for a firm price and lead time.

What is the breaking capacity of this MCCB at different voltages?

At 240 V AC it interrupts 121 kA; at 415 V AC it interrupts 76 kA. The rated operational voltage is 415 V AC, with DC operation supported up to 250 V.

What are the physical dimensions of 3VM1163-4ED22-0AA0?

Depth is 70 mm, width is 50.8 mm, height is 130 mm — a standard 2-pole MCCB footprint that fits existing SENTRON panel layouts.

What type of overcurrent release does this breaker use?

It uses a TM210 thermal-magnetic release with an adjustable instantaneous trip current (li) up to 630 A.