Skip to main content
Siemens 3VM1180-3EE32-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens SENTRON 3VM1180-3EE32-0AA0 MCCB, 80 A, 3-Pole, TM220

MPN3VM1180-3EE32-0AA0
Active

Siemens SENTRON 3VM1180-3EE32-0AA0, molded case circuit breaker, 3-pole, 80 A (40 °C), TM220 overcurrent release, 76 kA at 240 V.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VM1180-3EE32-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
3VM1180-3EE32-0AA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C80 A
Current at 45 °C80 A
Current at 50 °C80 A
Current at 55 °C78 A
Current at 60 °C77 A
Current at 65 °C75 A
Current at 70 °C74 A
Switching capacity classN
Breaking capacity at 240 V76 kA
Breaking capacity at 415 V53 kA
Breaking capacity at 440 V32 kA
Breaking capacity at 500 V12 kA
Power loss, max.19 W
3VM1180-3EE32-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM220
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VM1180-3EE32-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront connection
Protection class (IP), frontIP40
3VM1180-3EE32-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts0
3VM1180-3EE32-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VM1180-3EE32-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.15 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

It uses a TM220 thermal-magnetic overcurrent release, so it handles both overload and short-circuit faults in one unit. Rated 80 A at 40 °C, it carries that current up to 50 °C, then derates to 78 A at 55 °C, 77 A at 60 °C, 75 A at 65 °C, and 74 A at 70 °C — useful to know if your panel runs hot. Breaking capacity is 76 kA at 240 V, 53 kA at 415 V, 32 kA at 440 V, and 12 kA at 500 V. That 76 kA at 240 V gives you solid SCCR headroom for a 240 V distribution board — it interrupts high fault currents without cascading upstream.

Frequently asked questions

Where can I buy 3VM1180-3EE32-0AA0 and how is it quoted?

Sourced and quoted to order against an RFQ through independent distribution; availability and current pricing confirmed at quote time.

What is the breaking capacity of 3VM1180-3EE32-0AA0 at 240 V?

76 kA at 240 V, with 53 kA at 415 V, 32 kA at 440 V, and 12 kA at 500 V.

MPN