Protection settings and what they mean on the line
This breaker ships with a TM220 thermal-magnetic trip unit. The continuous current rating (In) is 80 A, with an adjustable overload protection band (Ir) from 56 A to 80 A — so you dial it in for the actual load, not just the frame size. The magnetic short-circuit pickup (Ii) is fixed at 10 times In, or 800 A. That's a standard motor-starting curve: it'll hold through an inrush without nuisance tripping, but clears fast on a bolted fault.