Skip to main content
Siemens 3VM1220-5EE42-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VM1220-5EE42-0AA0 SENTRON MCCB, 4-Pole, 200 A, TM22

MPN3VM1220-5EE42-0AA0
Active

Siemens SENTRON 3VM1220-5EE42-0AA0, 4-pole molded case circuit breaker, 200 A (40 °C), TM220 thermal-magnetic release, 187 kA at 240 V AC.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VM1220-5EE42-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VM1220-5EE42-0AA0 — Ratings
ParameterValue
Number of poles4
Current at 40 °C200 A
Current at 45 °C200 A
Current at 50 °C200 A
Current at 55 °C194 A
Current at 60 °C188 A
Current at 65 °C182 A
Current at 70 °C176 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V76 kA
Breaking capacity at 500 V30 kA
Power loss, max.42 W
3VM1220-5EE42-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM220
Overcurrent protection functionLI
Ground-fault monitoringWithout
3VM1220-5EE42-0AA0 — Construction & Connection
ParameterValue
Main circuit connector arrangementFront connection
Protection class (IP), frontIP40
3VM1220-5EE42-0AA0 — Accessories & Functions
ParameterValue
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts0
3VM1220-5EE42-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VM1220-5EE42-0AA0 — Mechanical
ParameterValue
Height158 mm
Width140 mm
Depth70 mm
Height (in)6.2 in
Width (in)5.5 in
Depth (in)2.8 in

Product details

SENTRON 3VM1220-5EE42-0AA0 — 200 A MCCB, 4-Pole, TM220

It uses a TM220 thermal-magnetic overcurrent release with an adjustable li (magnetic trip) up to 2,000 A. Breaking capacity is 187 kA at 240 V AC, 121 kA at 415 V, 76 kA at 440 V, and 30 kA at 500 V — enough headroom for most industrial fault-current scenarios without cascading upstream. Rated insulation voltage (Ui) is 690 V, and max DC operational voltage is 500 V, so it suits both AC and DC distribution panels.

Current rating vs. ambient temperature

The 200 A rating holds flat from 40 °C through 50 °C, then derates linearly to 176 A at 70 °C — useful when the breaker lives in a warm enclosure near other heat sources. Maximum power loss is 42 W, which factors into enclosure thermal calculations, especially in a multi-breaker lineup.

MPN
3VM1220-5EE42-0AA0