That means in a warm panel — say 55 °C internal ambient — you lose 8 A per pole; plan the load accordingly if you're pushing the 400 A bus.
At 240 V AC it interrupts 187 kA; at 415/440 V AC it's 121 kA; at 500 V AC it's 76 kA. If your transformer or generator can deliver 150 kA at 480 V, this breaker at 500 V (76 kA) won't be enough; step up to a higher interrupting-rated frame.
The 3-pole frame measures 138 mm wide, 248 mm tall, 110 mm deep — a standard MCCB footprint for 400 A class.