Skip to main content
Siemens 3VM1340-5ED42-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VM1340-5ED42-0AA0 SENTRON MCCB, 400A, 4-Pole, 187kA

MPN3VM1340-5ED42-0AA0
Active

Siemens SENTRON 3VM1340-5ED42-0AA0, molded case circuit breaker, 4-pole, 400 A rated current, TM210 thermal-magnetic trip, 187 kA interrupting at 240 V AC.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VM1340-5ED42-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection

Ratings

3VM1340-5ED42-0AA0 — Ratings
ParameterValue
Number of poles4
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C400 A
Current at 45 °C400 A
Current at 50 °C400 A
Current at 55 °C392 A
Current at 60 °C384 A
Current at 65 °C376 A
Current at 70 °C367 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V76 kA
Power loss, max.92 W

Protection & Trip Unit

3VM1340-5ED42-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout

Construction & Connection

3VM1340-5ED42-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront connection
Protection class (IP), frontIP40

Accessories & Functions

3VM1340-5ED42-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts0

Environmental

3VM1340-5ED42-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VM1340-5ED42-0AA0 — Mechanical
ParameterValue
Height248 mm
Width184 mm
Depth110 mm
Height (in)9.76 in
Width (in)7.24 in
Depth (in)4.33 in

Product details

400 A line protection with 187 kA interrupting capacity

The Siemens 3VM1340-5ED42-0AA0 is a SENTRON molded case circuit breaker (MCCB) sized for 400 A at 40 °C continuous, with a 4-pole configuration and a TM210 thermal-magnetic overcurrent release. Its interrupting rating of 187 kA at 240 V AC means it can safely clear a bolted fault at that level without upstream devices needing to coordinate — useful for high-fault-capacity service entrances or transformer secondaries where available fault current is substantial. Rated operational voltage is 690 V AC, with a rated insulation voltage of 800 V, so it suits 480Y/277 V and 600 V delta systems common in North American and European industrial panels. The 4-pole design handles three-phase plus neutral switching, or can be used on three-phase loads with the fourth pole as a switched neutral.

Thermal-magnetic trip and derating profile

The TM210 trip unit is a fixed thermal-magnetic type — no interchangeable rating plugs, no electronic adjustments. The thermal element tracks the 400 A rating up to 50 °C ambient; above that, the breaker derates linearly to 367 A at 70 °C. If the panel ambient runs hot (enclosed switchgear, solar combiner, or near a furnace line), the 55 °C figure of 392 A and the 60 °C figure of 384 A give you the actual continuous current the breaker can carry without nuisance tripping. Maximum power loss is 92 W at rated current — a factor for enclosure heat rise calculations when multiple breakers are ganged in a single panel. The IP40 front protection means the breaker face is sealed against tools and wires over 1 mm, but the enclosure itself must manage the heat dissipation.

Interrupting ratings across common system voltages

At 415 V and 440 V AC, the interrupting capacity holds at 121 kA; at 500 V it drops to 76 kA. For DC applications, the maximum rated operational voltage is 500 V DC — the manufacturer directs to the 3VA manual for specific DC switching capacity values, as the DC performance depends on the time constant and pole configuration.

Panel fit and mounting

Dimensions are 248 mm high, 184 mm wide, 110 mm deep — a standard 4-pole MCCB footprint that fits most Siemens SENTRON mounting plates and busbar systems. The 110 mm depth is the body depth; allow additional clearance for rear terminals and arc-chamber venting per the manufacturer's mounting instructions.

Frequently asked questions

What is the interrupting rating of 3VM1340-5ED42-0AA0 at 240 V?

187 kA at 240 V AC, which is the highest interrupting capacity on the spec sheet for this breaker.

What trip unit does this MCCB use?

A TM210 thermal-magnetic overcurrent release — fixed rating, no interchangeable trip plugs.

Where can I buy 3VM1340-5ED42-0AA0 and how is it quoted?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

MPN
3VM1340-5ED42-0AA0