Siemens 5SL4450-8 SENTRON 4-Pole MCB, D Curve, 50 A
The D curve suits loads with high inrush — motor starters, transformers, or welding equipment — where the magnetic trip holds off until roughly 10–20× rated current.
At 30 °C ambient the breaker carries the full 50 A; at 40 °C it derates to 47.36 A, at 45 °C to 46 A, and at 55 °C to 43.09 A.
Degree of pollution 2, overvoltage category III.