Skip to main content
Siemens 5SL4450-6CC — 4-Pole MCB (DIN Rail)

Siemens 5SL4450-6CC SENTRON MCB, 4P, 50 A, B-Curve, 10 kA

MPN5SL4450-6CC
Active

Siemens SENTRON 5SL4450-6CC, 4-pole miniature circuit breaker, 50 A rated current, B tripping characteristic, 10 kA breaking capacity (EN 60898), 400 V AC, 4 width units.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SL4450-6CC — Identification
ParameterValue
Type / order code5SL4CC
Brand nameSENTRON
Application suitabilityResidential buildings/infrastructure
5SL4450-6CC — Ratings
ParameterValue
Number of poles4
Pole configuration4P
Rated current (In), AC50 A
Rated voltage, AC (multi-phase)440 V
Rated voltage, DC (max.)60 V
Voltage typeAC
Rated frequency50 Hz
5SL4450-6CC — Protection
ParameterValue
Tripping characteristic (trip curve)B
Rated breaking capacity (Icn), per EN 6089810 kA
Overvoltage category3
Degree of protection (IP)IP20, with connected conductors
Neutral conductor switchingNo
Touch protectionYes
5SL4450-6CC — Mechanical
ParameterValue
Width in modular units4
Width72 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Mounting positionany
SealableYes
5SL4450-6CC — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes
Influence of ambient temperature (derating)+55 °C, max. 95% humidity

Product details

The Siemens 5SL4450-6CC is a SENTRON 5SL miniature circuit breaker, 4-pole (4P), rated 50 A at AC with a B tripping characteristic. It breaks fault currents up to 10 kA per EN 60898 at 400 V AC — the standard for residential and light commercial distribution panels.

50 A at 400 V AC is the continuous current per phase — this breaker protects a 50 A feeder or submain. The 10 kA breaking capacity (Icn) per EN 60898 means it can safely interrupt a short-circuit fault up to 10,000 A at the rated voltage; that covers most residential and light commercial service entrances where the prospective fault current stays under that threshold. The B-curve (3–5× In) avoids nuisance trips on lighting or resistive loads but will trip faster than a C-curve on moderate inrush. Terminal capacity accepts solid or stranded conductors from 0.75 to 25 mm², with a tightening torque of 2.5 to 3 N·m — enough for 25 mm² tails on a 50 A feed.

Deployment context

Ambient temperature range -25 to +55 °C operating, with storage from -40 to +75 °C. Halogen-free and silicon-free construction suits environments where outgassing must be minimized (data centers, clean manufacturing).

Frequently asked questions

Who supplies 5SL4450-6CC and how is it quoted for volume purchases?

The 5SL4450-6CC is sourced through independent distribution and quoted to order against an RFQ. Availability and current pricing are confirmed at quote time.

What is 5SL4450-6CC's listed depth (76 mm) on this component line?

The 5SL4450-6CC has a depth of 76 mm, a width of 72 mm (4 width units), and a height of 90 mm. Installation depth is 70 mm.

What compliance documentation does this brand provide for 5SL4450-6CC (RoHS, REACH, UL, IEC)?

The 5SL4450-6CC is designed per EN 60898 (breaking capacity 10 kA) and carries an overvoltage category 3 rating. It is halogen-free and silicon-free. For specific RoHS, REACH, or UL documentation, request the manufacturer's declaration with your RFQ.

MPN
5SL4450-6CC