Skip to main content
Siemens 5SL4663-7 — 4-Pole MCB (DIN Rail)

Siemens 5SL4663-7 SENTRON MCB, 63 A C-Curve, 3P+N, 10 kA

MPN5SL4663-7
Active

Siemens SENTRON 5SL4663-7, miniature circuit breaker, 3P+N, 63 A, C-curve, 400 V AC, 10 kA breaking capacity, 4 MWU.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SL4663-7 — Identification
ParameterValue
Brand nameSENTRON
Application suitabilityResidential buildings/infrastructure
5SL4663-7 — Ratings
ParameterValue
Number of poles4
Pole configuration3P+N
Rated voltage, AC (multi-phase)440 V
5SL4663-7 — Protection
ParameterValue
Tripping characteristic (trip curve)C
Energy limitation class3
Overvoltage categoryIII
Pollution degree2
Degree of protection (IP)IP20, with connected conductors
5SL4663-7 — Mechanical
ParameterValue
Width in modular units4
Width72 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Mounting positionany
Tightening torque, max.75 °C
Tightening torque, min.-40 °C
SealableYes
5SL4663-7 — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes
5SL4663-7 — Performance
ParameterValue
Power loss per pole, AC (hot state, at In)5 W

Product details

The Siemens SENTRON 5SL4663-7 is a 4-pole (3P+N) miniature circuit breaker rated 63 A with a C-curve trip characteristic, designed for 400 V AC multi-phase circuits and delivering 10 kA breaking capacity per both EN 60898 and IEC 60947-2. At 63 A and 4 modular width units (72 mm wide), this is the high-current end of the 5SL6 family; it occupies four 18 mm DIN-rail slots.

The 10 kA breaking capacity is the same under both EN 60898 (household standard) and IEC 60947-2 (industrial standard), so this breaker qualifies for either classification without derating. The 400 V AC rated voltage with a 440 V AC maximum on multi-phase operation means it handles standard 230/400 V three-phase networks cleanly, with headroom for nominal line swell. DC rated at 72 V maximum — usable for DC distribution only at low voltage, not for 125 V DC battery banks.

Snap-on DIN rail mounting, any position. The 72 mm width (4 MWU) is the same footprint as four single-pole breakers ganged; verify your enclosure's gland-plate knockout pattern if you're swapping from a 3-pole unit. Sealable (padlockable toggle) for lockout/tagout compliance.

Frequently asked questions

Will 5SL4663-7 drop into a panel that was specified around 5SL4363-7 without rewiring?

The 5SL4663-7 (3P+N, 72 mm wide) is one modular width unit wider than the 5SL4363-7 (3P, 54 mm wide). It mounts on the same DIN rail but occupies four slots instead of three. Verify your enclosure's fill factor and busbar alignment — the neutral pole adds a terminal that the 3-pole version lacks, so the downstream wiring changes.

MPN
5SL4663-7