Rated breaking capacity is 10 kA per IEC/EN 60898-1 and 20 kA per IEC 60947-2, with a further 15 kA at DC (60 V per pole) per IEC 60947-2. That dual rating means it meets the higher fault-current demands of industrial panel coordination (60947-2) while also qualifying for residential and commercial final circuits under 60898-1. Depth is 76 mm (70 mm installation depth), so it sits flush with standard distribution board covers. The IP20 rating applies with conductors connected — expected for a panel-mount device.
Certifications and compliance
Certified to IEC/EN 60898-1 and IEC/EN 60947-2, with additional UL 1077 and CSA C22.2 No. 235 recognition (5 kA at AC). The housing is sealable — a feature for panel builders who need to lock out adjustment after commissioning.
Environmental range
Operates from -40 °C to 75 °C ambient, with humidity derating: 95% RH up to 55 °C, 55% RH to 70 °C, and 35% RH to 75 °C. That -40 °C floor is relevant for unheated enclosures in cold climates or refrigerated areas.