Thermal derating and ambient range
Rated 1 A at 35 °C; derates to 0.85 A at 60 °C. The full operating range spans -40 °C to 75 °C, with humidity limits of 95% RH up to 55 °C, tapering to 35% RH at 75 °C. In a warm panel (say 50 °C internal ambient), expect 0.9 A continuous — factor that into the load schedule. Halogen-free and silicon-free construction avoids outgassing issues in sealed enclosures.