Siemens 5SY4301-8 — 3-Pole MCB (DIN Rail)

Siemens 5SY4301-8 SENTRON 3-Pole MCB, D Curve, 1 A, 10 kA

MPN5SY4301-8
Active

Siemens SENTRON 5SY4301-8, 3-pole miniature circuit breaker, D tripping characteristic, rated current 1 A at 35 °C, breaking capacity 10 kA per EN 60898 / 35 kA per IEC 60947-2.

$53.34Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

5SY4301-8 — Identification
ParameterValue
Brand nameSENTRON
Number of poles3
Pole configuration3P
Suitability for operationMechanical engineering / industry
5SY4301-8 — Protection
ParameterValue
Tripping characteristic (curve)D
Overvoltage categoryIII
IP protection classIP20, with connected conductors
Pollution degree3
5SY4301-8 — Electrical
ParameterValue
Rated current (AC)1 A
Rated voltage (AC, multi-phase)440 V
5SY4301-8 — Mechanical
ParameterValue
Modular width units3
Mounting positionany
Width54 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Terminal tightening torque, max.75 °C
Terminal tightening torque, min.-40 °C
Combined terminal, topYes
Combined terminal, bottomYes
Fastening methodQuick assembly system
SealableYes
5SY4301-8 — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes
Influence of surrounding temperaturemax. 95% to 55°C, max. 55% to 70°C, max. 35% to 75°C

Product details

Breaking capacity and dual-standard rating

The 5SY4301-8: This MCB carries two breaking-capacity ratings: 10 kA under EN 60898-1 and 35 kA under IEC 60947-2 / UL1077. The higher 35 kA figure applies when the breaker is used as a supplementary protector per 60947-2 — important for panel builders who need to coordinate with upstream fault levels above 10 kA.

Temperature derating and panel placement

The 5SY4301-8 is rated 1 A at 35 °C, but derates to 0.95 A at 40 °C, 0.93 A at 45 °C, 0.9 A at 50 °C, 0.88 A at 55 °C, and 0.85 A at 60 °C. In a crowded DIN-rail enclosure with multiple breakers side by side, ambient temperature near the breaker can rise 10–15 °C above the room — factor the derated current into the load calculation, not the 35 °C figure. Mounts in any position, and the quick-assembly system snaps onto the rail without tools.

Frequently asked questions

What is the datasheet for Siemens 5SY4301-8?

Engineers need to validate fit, form, and electrical ratings before designing in the part.

Where can I buy Siemens 5SY4301-8 in stock?

Sourcing buyers need immediate inventory availability to fill BOM lines without delay.

What is the price of Siemens 5SY4301-8?

Commercial pricing directly impacts procurement decisions and budget planning.

What is the replacement or equivalent for 5SY4301-8?

Technicians and brokers need cross-reference options for obsolete stock or alternative sourcing.

Is the Siemens 5SY4301-8 a 3-pole MCB with D curve?

Quick confirmation of polarity and trip curve prevents ordering errors in critical applications.

What is the breaking capacity of 5SY4301-8?

Breaking capacity is essential for ensuring the circuit breaker can safely interrupt fault currents.

MPN
5SY4301-8