Thermal derating — the number that matters at panel ambient
The 1 A rating holds at 35 °C. Above that, the MCB derates: 0.95 A at 40 °C, 0.93 A at 45 °C, 0.9 A at 50 °C, 0.88 A at 55 °C, and 0.85 A at 60 °C. If your panel ambient runs 50 °C, figure 0.9 A continuous — a 10 % reduction that can nuisance-trip a borderline load.