Skip to main content
Siemens 5SY4301-7CC11 — 3-Pole MCB (DIN Rail)

Siemens 5SY4301-7CC11 SENTRON MCB, 3P, 1A, C-Curve, 10 kA

MPN5SY4301-7CC11

Siemens SENTRON 5SY4301-7CC11 miniature circuit breaker, 3-pole, 1 A rated current, C tripping characteristic, 10 kA breaking capacity per EN 60898, 400 V AC, for railway applications.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SY4301-7CC11 — Identification
ParameterValue
Brand nameSENTRON
Number of poles3
Suitability for operationMechanical engineering / industry
5SY4301-7CC11 — Protection
ParameterValue
Tripping characteristic (curve)C
Breaking capacity per EN 6089810 kA
Overvoltage categoryIII
IP protection classIP20, with connected conductors
5SY4301-7CC11 — Electrical
ParameterValue
Rated current (AC)400 V
Rated voltage (AC, multi-phase)440 V
Rated frequency50/60 Hz
5SY4301-7CC11 — Mechanical
ParameterValue
Mounting positionany
Width54 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Terminal tightening torque, max.31 lbf·in
Terminal tightening torque, min.22 lbf·in
Combined terminal, topYes
Combined terminal, bottomYes
SealableYes
5SY4301-7CC11 — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes
Influence of surrounding temperaturemax. 95% to 55°C, max. 55% to 70°C, max. 35% to 75°C

Product details

Mounts via the quick-assembly system (DIN rail) in any position — no derating needed for horizontal or inverted orientation. The 3-pole body occupies 3 width units (54 mm) on the rail, with a depth of 76 mm and an installation depth of 70 mm behind the panel surface. IP20 with connected conductors is standard for enclosed distribution boards; the sealable option lets the panel builder lock the toggle position to prevent unauthorized switching during commissioning or maintenance.

Energy limiting class 3 means this MCB limits the let-through energy (I²t) to a low level, which improves downstream device protection and aids selective coordination with upstream breakers. The 10 kA SCCR at 400 V AC covers most industrial panel fault levels; for higher available fault currents, verify the upstream device's let-through curve against the MCB's withstand. Combined top and bottom terminals allow loop-through wiring without extra busbars — a time-saver on the panel wireman's bench.

Frequently asked questions

What is the breaking capacity of the 5SY4301-7CC11?

10 kA per EN 60898 at 400 V AC. This is the standard breaking capacity for the SENTRON 5SY4 series and suits most industrial distribution boards.

Where can I buy the 5SY4301-7CC11?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commitment.

What compliance documentation does Siemens provide for this MCB?

The 5SY4301-7CC11 carries EN 60898 certification for breaking capacity and is designed for railway applications, which implies compliance with EN 50155. The halogen-free and silicon-free declaration supports RoHS and REACH alignment. Specific certificates (UL, CSA, IEC) should be confirmed from the manufacturer's documentation package.

MPN