The breaker carries approvals to IEC / EN 60898-1, IEC / EN 60947-2, and UL 1077 / CSA C22.2 No. 235. That means it is accepted in European (CE-marked) and North American (UL/CSA) installations — a single SKU for multi-region panels. Energy limitation class 3 limits let-through energy, reducing downstream damage on a fault. No neutral conductor switching; this is a straight 3-pole device for line-side protection only.
Siemens 5SY4363-6 SENTRON MCB, 3P, B-Curve, 10kA IEC
Siemens SENTRON 5SY4363-6, 3-pole miniature circuit breaker, B characteristic, 10 kA (EN 60898) / 15 kA (IEC 60947-2), 400 V AC, 60 V DC.
Specifications
| Parameter | Value |
|---|---|
| Brand name | SENTRON |
| Number of poles | 3 |
| Pole configuration | 3P |
| Suitability for operation | Mechanical engineering / industry |
| Parameter | Value |
|---|---|
| Tripping characteristic (curve) | B |
| Breaking capacity per EN 60898 | 10 kA |
| Breaking capacity per IEC 60947-2 | 15 kA |
| Overvoltage category | III |
| IP protection class | IP20, with connected conductors |
| Energy limitation class | 3 |
| Pollution degree | 3 |
| Parameter | Value |
|---|---|
| Rated voltage (AC, multi-phase) | 440 V |
| Voltage type (AC/DC) | AC |
| Supply frequency range | 50/60 Hz |
| Power loss per pole at rated current (AC, hot) | 6 W |
| Mechanical service life (operating cycles, typ.) | 10 000 |
| Neutral conductor switching | No |
| Rated voltage (AC, single-phase) | 440 V |
| Parameter | Value |
|---|---|
| Modular width units | 3 |
| Mounting position | any |
| Width | 54 mm |
| Height | 90 mm |
| Depth | 76 mm |
| Installation depth | 70 mm |
| Terminal tightening torque, max. | 75 °C |
| Terminal tightening torque, min. | -40 °C |
| Combined terminal, top | Yes |
| Combined terminal, bottom | Yes |
| Fastening method | Quick assembly system |
| Sealable | Yes |
| Accepts supplementary devices | Yes |
| Parameter | Value |
|---|---|
| Halogen-free | Yes |
| Silicone-free | Yes |
| Influence of surrounding temperature | max. 95% to 55°C, max. 55% to 70°C, max. 35% to 75°C |
| Vibration resistance (IEC 60068-2-6) | ±1mm at 5 to 25Hz; 50m/s² at 25 to 150Hz |
Product details
Frequently asked questions
Where can I buy 5SY4363-6 and how do I get a price?
The part is available to quote on request. Submit an RFQ through this listing; availability and current pricing are confirmed at quote time. No stock count or price is displayed here.
Will 5SY4363-6 drop into a panel specified around 5SY4140-7 without rewiring?
No. The 5SY4140-7 is a different pole/current variant in the same SENTRON family, but the 5SY4363-6 is a 3-pole B-curve breaker with a specific interrupting capacity and terminal layout. It shares the same DIN-rail footprint (3 MW, 54 mm wide) but the electrical ratings differ — verify the branch circuit requirements before substituting.
What compliance documentation does Siemens provide for 5SY4363-6?
The breaker is certified to IEC / EN 60898-1, IEC / EN 60947-2, and UL 1077 / CSA C22.2 No. 235. It is halogen-free and silicon-free. Standard RoHS and REACH declarations are available from Siemens upon request.