It handles 400 V AC and delivers a 10 kA breaking capacity per EN 60898, with a higher 35 kA rating per IEC 60947-2 — the figure that governs selectivity in an industrial panel.
The 10 kA EN 60898 rating is the residential/commercial ceiling; the 35 kA figure is what an industrial engineer sizes against. Terminals accept solid or stranded conductors from 0.75 to 35 mm² — that covers everything from control wiring (1.5 mm²) up to the main feeder (25 or 35 mm²). Combined terminals top and bottom mean you can feed through or loop out without separate busbar connectors. The breaker is sealable (tamper-evident seal wire possible) and carries touch protection per the IP20 rating once conductors are connected.
The design is explicitly for railway applications (vibration and shock tolerance) and mechanical engineering / industry environments.