Skip to main content
Siemens 5SY4416-7KK11 — 4-Pole MCB (DIN Rail)

Siemens 5SY4416-7KK11 SENTRON MCB, 4P C-curve 16 A, 10/20 kA

MPN5SY4416-7KK11

Siemens SENTRON miniature circuit breaker, 5SY4416-7KK11, 4-pole (4P), tripping characteristic C, rated current 16 A at 35 °C, breaking capacity 10 kA acc. to EN 60898 / 20 kA acc. to IEC 60947-2.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

5SY4416-7KK11 — Identification
ParameterValue
Brand nameSENTRON
Application suitabilityMechanical engineering / industry
5SY4416-7KK11 — Ratings
ParameterValue
Number of poles4
Pole configuration4P
Rated current (In), AC16 A
Rated voltage, AC (multi-phase)440 V
Rated voltage, AC (single-phase)440 V
Voltage typeAC
5SY4416-7KK11 — Protection
ParameterValue
Tripping characteristic (trip curve)C
Rated breaking capacity (Icn), per EN 6089810 kA
Rated breaking capacity, per IEC 60947-220 kA
Breaking capacity, AC (UL 1077 / CSA C22.2 No.235)5 kA
Energy limitation class3
Overvoltage categoryIII
Pollution degree3
Degree of protection (IP)IP20, with connected conductors
Neutral conductor switchingNo
Touch protectionYes
5SY4416-7KK11 — Mechanical
ParameterValue
Width in modular units4
Width72 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Fastening / mounting methodQuick assembly system
Mounting positionany
Combined terminal, topYes
Combined terminal, bottomYes
Tightening torque, max.75 °C
Tightening torque, min.-40 °C
SealableYes
5SY4416-7KK11 — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes
Influence of ambient temperature (derating)max. 95% to 55°C, max. 55% to 70°C, max. 35% to 75°C

Product details

Integration and mounting

Mounts on DIN rail via the quick assembly system in any position. Occupies 4 modular width units — that's 72 mm width on the rail. Depth is 76 mm, with an installation depth of 70 mm behind the panel surface. Height is 90 mm. The combined terminal top and bottom accept conductors from either direction, simplifying busbar routing. IP20 with connected conductors — protected against finger touch but not moisture, so install inside a rated enclosure. Overvoltage category III and pollution degree 3 suit fixed installations in industrial environments where transient overvoltages are common.

Frequently asked questions

Where can I buy 5SY4416-7KK11 and how do I get a price?

This part is available to order through independent distribution. Submit an RFQ; availability and current pricing are confirmed at quote time. No stock count or price is listed here.

What is the breaking capacity of 5SY4416-7KK11?

10 kA per EN 60898 and 20 kA per IEC 60947-2. Use the IEC 60947-2 figure for industrial panel SCCR calculations.

Will 5SY4416-7KK11 drop into a panel specified around 5SY4140-7 without rewiring?

Both are 4-pole SENTRON MCBs on the same DIN-rail footprint (4 MW, 72 mm wide). The 5SY4416-7KK11 is a 16 A C-curve; the 5SY4140-7 is a 40 A C-curve. If the panel busbars and load wiring are sized for 40 A, installing a 16 A breaker is fine — the breaker protects downstream, not upstream. No rewiring of the rail or terminals is needed.

MPN
5SY4416-7KK11