Siemens 5SY4416-7CC11 — 4-Pole MCB (DIN Rail)

Siemens 5SY4416-7CC11 SENTRON MCB, 4P C 16A 10kA, 400V AC

MPN5SY4416-7CC11

Siemens SENTRON 5SY4416-7CC11, 4-pole miniature circuit breaker, C-curve, 16 A rated current, 10 kA breaking capacity at 400 V AC, 4 width units (72 mm).

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SY4416-7CC11 — Identification
ParameterValue
Brand nameSENTRON
Application suitabilityMechanical engineering / industry
5SY4416-7CC11 — Ratings
ParameterValue
Number of poles4
Pole configuration4P
Rated current (In), AC400 V
Rated current (In), AC16 A
Rated voltage, AC (multi-phase)440 V
Rated voltage, AC (single-phase)440 V
Rated voltage, DC (max.)72 V
Voltage typeAC
Rated frequency50/60 Hz
5SY4416-7CC11 — Protection
ParameterValue
Tripping characteristic (trip curve)C
Rated breaking capacity (Icn), per EN 6089810 kA
Overvoltage categoryIII
Degree of protection (IP)IP20, with connected conductors
Neutral conductor switchingNo
Touch protectionYes
5SY4416-7CC11 — Mechanical
ParameterValue
Width in modular units4
Width72 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Mounting positionany
Combined terminal, topYes
Combined terminal, bottomYes
SealableYes
5SY4416-7CC11 — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes
Influence of ambient temperature (derating)max. 95% to 55°C, max. 55% to 70°C, max. 35% to 75°C
5SY4416-7CC11 — Performance
ParameterValue
Mechanical service life (switching cycles, typ.)10 000

Product details

What it is and what it does

The Siemens 5SY4416-7CC11 is a SENTRON miniature circuit breaker (MCB) designed for 4-pole (4P) AC branch-circuit protection. Its C-curve tripping characteristic means it handles moderate inrush currents typical of motor starters, transformers, and capacitor banks — it trips between 5 and 10 times rated current on a short circuit, so it won't nuisance-trip on a pump or conveyor start, but clears a hard fault fast enough to protect downstream wiring. Rated 16 A at 400 V AC, with a 10 kA breaking capacity per EN 60898. That 10 kA figure is the maximum fault current it can safely interrupt at 400 V without welding its contacts or venting arc plasma into the panel — critical for selectivity studies in a distribution board where upstream breakers must see the fault and stay closed. Energy limiting class 3 means it restricts let-through energy (I²t) to the lowest band per EN 60898, reducing thermal stress on downstream components during a fault. For a panel builder, that translates to smaller cable sizing and less arc-flash energy at the load side.

Frequently asked questions

What is the closest functional second-source for the 5SY4416-7CC11 — the 5SY6613-8?

The 5SY6613-8 is a different pole count and rating; it will not drop into the same panel position without rewiring. The 5SY4416-7CC11 is a 4-pole, 16 A, C-curve MCB. If you need a direct functional substitute, verify the pole count, current, and breaking capacity against your BOM — do not assume a different order code is a drop-in replacement.

What conductor sizes does the 5SY4416-7CC11 accept?

Solid and stranded conductors from 0.75 to 35 mm². The screw-type terminals accept that full range without reducing the lug.

Will the 5SY4416-7CC11 drop into a panel specified around the 5SY6613-8 without rewiring?

No. The 5SY6613-8 is a different pole count and rating. The 5SY4416-7CC11 is a 4-pole device; the 5SY6613-8 is not. The DIN-rail footprint may differ in width units. Panel wiring and busbar configuration would need to be verified against the original specification.