Designed for railway applications per its designation, it also suits general mechanical engineering and industrial panels.
At 20 A it feeds a 20 A sub-feed or a group of smaller circuits. The temperature derating table is published: at 40 °C it carries 19.04 A, at 50 °C it carries 18.04 A, at 60 °C it carries 16.96 A — so if your panel ambient runs hot, you need to account for that.
Sealable, halogen-free, silicon-free — suitable for environments where outgassing or contamination matters. Touch protection is built in.