Skip to main content
Siemens 5SY5450-6 — 4-Pole MCB (DIN Rail)

Siemens 5SY5450-6 SENTRON MCB, 4P B-Curve, 10kA, 400V AC

MPN5SY5450-6
Active

Siemens SENTRON 5SY5450-6, 4-pole miniature circuit breaker, B-curve, 10 kA (IEC 60898-2), 15 kA DC (IEC 60947-2), 400 V AC, 72 mm wide, IP20.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

5SY5450-6 — Identification
ParameterValue
Brand nameSENTRON
Application suitabilityuniversal current
5SY5450-6 — Ratings
ParameterValue
Number of poles4
Pole configuration4P
Rated voltage, AC (multi-phase)440 V
5SY5450-6 — Protection
ParameterValue
Tripping characteristic (trip curve)B
Energy limitation class3
Overvoltage categoryII
Pollution degree2
Degree of protection (IP)IP20, with connected conductors
5SY5450-6 — Mechanical
ParameterValue
Width in modular units4
Width72 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Fastening / mounting methodQuick assembly system
Mounting positionany
Combined terminal, topYes
Combined terminal, bottomYes
Tightening torque, max.75 °C
Tightening torque, min.-40 °C
SealableYes
5SY5450-6 — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes
Influence of ambient temperature (derating)max. 95% to 55°C, max. 55% to 70°C, max. 35% to 75°C
5SY5450-6 — Performance
ParameterValue
Power loss per pole, AC (hot state, at In)4.3 W

Product details

Siemens 5SY5450-6 SENTRON MCB — 4-pole B-curve, 10 kA

Rated 10 kA breaking capacity per IEC / EN 60898-2 and 15 kA at DC per IEC 60947-2, it handles 400 V AC multi-phase supply (440 V single-phase) and 880 V DC (max 1000 V DC operating voltage). Universal-current rated — AC or DC, polarity matters on DC side per the manufacturer's note. The 10 kA IEC rating covers most commercial panel fault levels; the 15 kA DC rating at 1000 V makes it usable in DC bus or battery-string protection where higher interrupting capacity is needed.

Snap-on DIN-rail mount via quick assembly system, any orientation. IP20 with connected conductors; sealable (tamper-evident cover available). Combined terminals top and bottom — line and load can land on either side, no orientation restriction. Halogen-free and silicon-free construction for clean-room or sensitive electronics environments.

Current production — no end-of-life notice. Dual-standard certified: IEC / EN 60898-2 and UL1077. Overvoltage category II, pollution degree 2. Energy limitation class 3. Vibration rated per IEC 60068-2-6: ±1 mm at 5–25 Hz, 50 m/s² at 25–150 Hz — suitable for machine-mounted panels or transport applications.

Frequently asked questions

Will 5SY5450-6 drop into a panel specified around 5SY4140-7 without rewiring?

Yes — both are 4-pole SENTRON MCBs with the same 72 mm width (4 modular units), 76 mm depth, and quick-assembly DIN-rail mount. Terminal arrangement and combined top/bottom entry are identical. No rewiring needed for the physical fit; verify the B-curve rating matches your circuit design.

What compliance documentation does this brand provide for 5SY5450-6?

The part is certified to IEC / EN 60898-2 and UL1077. It is halogen-free and silicon-free. Standard compliance documentation (declaration of conformity, UL recognition file) is available from Siemens for this SENTRON series.

MPN
5SY5450-6