The DC rating matches the 15 kA figure at up to 72 V DC, so it works on DC control buses as well. Rated 400 V AC phase-to-phase, 440 V max for single- or multi-phase operation.
Mounting position any — no derating for horizontal or vertical orientation. Terminal design accepts top and bottom combined terminals; neutral conductor switching is not built in (no switched neutral pole). Pollution degree 3, overvoltage category III — standard for fixed-installation distribution boards.
Certified to IEC/EN 60898-1 and IEC/EN 60947-2, plus UL 1077 and CSA C22.2 No. 235. The UL 1077 rating is 5 kA — that's the supplementary-protector limit for North American panels where the MCB is not the sole branch-circuit overcurrent device. Halogen-free and silicon-free construction, sealable for lockout/tagout.