Skip to main content
Siemens 5SY7610-7 — 4-Pole MCB (DIN Rail)

Siemens 5SY7610-7 SENTRON MCB, 4P C-curve, 15/30 kA

MPN5SY7610-7
Active

Siemens SENTRON 5SY7610-7, 4-pole (3P+N) miniature circuit breaker, C-curve, 15 kA per EN 60898-1 / 30 kA per IEC 60947-2, 400 V AC, 4 MW DIN-rail mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SY7610-7 — Identification
ParameterValue
Brand nameSENTRON
Application suitabilityMechanical engineering / industry
5SY7610-7 — Ratings
ParameterValue
Number of poles4
Pole configuration3P+N
Rated voltage, AC (multi-phase)440 V
5SY7610-7 — Protection
ParameterValue
Tripping characteristic (trip curve)C
Energy limitation class3
Overvoltage categoryIII
Pollution degree3
Degree of protection (IP)IP20, with connected conductors
5SY7610-7 — Mechanical
ParameterValue
Width in modular units4
Width72 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Fastening / mounting methodQuick assembly system
Mounting positionany
Combined terminal, topYes
Combined terminal, bottomYes
Tightening torque, max.75 °C
Tightening torque, min.-40 °C
SealableYes
5SY7610-7 — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes
Influence of ambient temperature (derating)max. 95% to 55°C, max. 55% to 70°C, max. 35% to 75°C
5SY7610-7 — Performance
ParameterValue
Power loss per pole, AC (hot state, at In)1.1 W

Product details

What this 4-pole MCB brings to the panel

The Siemens 5SY7610-7 is a 4-pole (3P+N) SENTRON miniature circuit breaker with a C-curve trip characteristic, meaning it's built for moderate inrush loads like motor starters and small transformers where the magnetic trip kicks in at 5–10× rated current. The neutral pole is switched, so you get full isolation on all four poles in a single 4-module-width package — no separate neutral link needed. Breaking capacity is dual-rated: 15 kA per EN 60898-1 and 30 kA per IEC 60947-2, with a DC rating of 15 kA at 60 V per IEC 60947-2 and 5 kA per UL 1077 / CSA C22.2 No.235. DC side is rated at 60 V, max 72 V. Frequency is 50/60 Hz.

Standards and compliance — what the approvals mean

This breaker carries triple certification: IEC / EN 60898-1 (the residential and light-commercial standard for MCBs), IEC / EN 60947-2 (the industrial standard for circuit breakers), and UL 1077 (the supplementary protector standard for North America). That means it's accepted in European, UK, and North American panels — one part number covers multiple regulatory jurisdictions. Halogen-free and silicon-free construction reduces toxic smoke and corrosive byproducts in a fault event — relevant for panels in occupied spaces or sensitive electronics areas. The sealable option lets you lock the toggle position to prevent unauthorized reset after a trip.

Mounting and integration — DIN-rail fit

That 72 mm width equals 4 modular units — a standard 4-pole MCB footprint that drops into any 35 mm DIN-rail panel without surprises. IP20 protection with connected conductors — standard for inside the enclosure; no special sealing required. Combined terminals on both top and bottom accept supply from either end, so you can bus the line side without reconfiguring the breaker.

Frequently asked questions

What is the breaking capacity of the 5SY7610-7?

The 5SY7610-7 is dual-rated: 15 kA per EN 60898-1 and 30 kA per IEC 60947-2 at 400 V AC. For DC circuits it's rated 15 kA at 60 V per IEC 60947-2, and 5 kA per UL 1077.

What standards does the 5SY7610-7 comply with?

It complies with IEC / EN 60898-1, IEC / EN 60947-2, and UL 1077 / CSA C22.2 No.235. It is also halogen-free and silicon-free, with pollution degree 3 and overvoltage category III ratings.

Where can I buy the 5SY7610-7 and get current pricing?

The 5SY7610-7 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

Will the 5SY7610-7 drop into a panel specified for the 5SY4140-7?

Both are 4-pole SENTRON MCBs on the same DIN-rail footprint, so the mechanical fit is the same. The key difference is the 5SY7610-7 carries a C-curve versus whatever curve the 5SY4140-7 variant specifies — verify the trip characteristic matches your coordination study before swapping.

MPN
5SY7610-7