Siemens 5SY7608-8 — 4-Pole MCB (DIN Rail)

Siemens SENTRON 5SY7608-8 MCB, D Curve, 8 A, 4-Pole, 15/30 k

MPN5SY7608-8
Active

Siemens SENTRON miniature circuit breaker, 5SY7608-8, D characteristic, 8 A, 4-pole (3P+N), 15 kA per EN 60898, 30 kA per IEC 60947-2.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SY7608-8 — Identification
ParameterValue
Brand nameSENTRON
Application suitabilityMechanical engineering / industry
5SY7608-8 — Ratings
ParameterValue
Number of poles4
Pole configuration3P+N
Rated current (In), AC400 V
Rated voltage, AC (multi-phase)440 V
Rated voltage, AC (single-phase)440 V
Voltage typeAC
5SY7608-8 — Protection
ParameterValue
Tripping characteristic (trip curve)D
Rated breaking capacity (Icn), per EN 6089815 kA
Rated breaking capacity, per IEC 60947-230 kA
Breaking capacity, AC (UL 1077 / CSA C22.2 No.235)5 kA
Overvoltage categoryIII
Pollution degree3
Degree of protection (IP)IP20, with connected conductors
Neutral conductor switchingYes
Touch protectionYes
5SY7608-8 — Mechanical
ParameterValue
Width in modular units4
Width72 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Fastening / mounting methodQuick assembly system
Mounting positionany
Combined terminal, topYes
Combined terminal, bottomYes
Tightening torque, max.75 °C
Tightening torque, min.-40 °C
SealableYes
5SY7608-8 — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes
Influence of ambient temperature (derating)max. 95% to 55°C, max. 55% to 70°C, max. 35% to 75°C

Product details

What the ratings mean for fit

The Siemens SENTRON 5SY7608-8 is a 4-pole miniature circuit breaker (3P+N) with a D tripping characteristic, rated 8 A at 35 °C. The D curve means it tolerates high inrush currents — typically 10–20× rated current before instantaneous trip — so it is sized for motor, transformer, or heavy inductive loads where a B or C curve would nuisance-trip on startup. Breaking capacity is 15 kA under EN 60898 and 30 kA under IEC 60947-2, giving headroom for high-fault industrial panels. At 400 V AC, overvoltage category III, pollution degree 3 — standard for fixed-installation distribution boards.

Temperature derating — real-world current

Rated current drops with ambient temperature: 8 A at 35 °C, 7.26 A at 45 °C, 6.99 A at 50 °C, 6.72 A at 55 °C, 6.43 A at 60 °C. If the breaker lives in a warm enclosure or next to other heat sources, size the load to the derated value at the expected ambient — not the 35 °C figure.

Mounting and integration

Snaps onto DIN rail via the quick-assembly system; 4 modular width units (72 mm wide). Mounting position any — vertical or horizontal in the panel. Installation depth 70 mm plus conductor space; overall depth 76 mm. IP20 with connected conductors — protected against finger contact but not washdown; keep inside the enclosure. Combined terminals top and bottom accept standard copper conductors. Sealable, halogen-free, silicon-free — suitable for clean-room or low-outgassing environments.

Lifecycle and sourcing

Current production — no end-of-life notice. Sourced and quoted to order against an RFQ through independent distribution.