Skip to main content
Siemens 5SY8613-7 — 4-Pole MCB (DIN Rail)

Siemens 5SY8613-7 SENTRON MCB, 4P C-Characteristic, 400V AC

MPN5SY8613-7
Active

Siemens SENTRON 5SY8613-7, 4-pole miniature circuit breaker, C-tripping characteristic, 400 V AC, 30 kA breaking capacity per IEC 60947-2.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SY8613-7 — Identification
ParameterValue
Brand nameSENTRON
Application suitabilityMechanical engineering / industry
5SY8613-7 — Ratings
ParameterValue
Number of poles4
Pole configuration3P+N
Rated current (In), AC400 V
Rated voltage, AC (multi-phase)440 V
Rated voltage, AC (single-phase)440 V
Voltage typeAC
5SY8613-7 — Protection
ParameterValue
Tripping characteristic (trip curve)C
Rated breaking capacity, per IEC 60947-230 kA
Breaking capacity, AC (UL 1077 / CSA C22.2 No.235)5 kA
Overvoltage categoryIII
Pollution degree3
Degree of protection (IP)IP20, with connected conductors
Neutral conductor switchingYes
Touch protectionYes
5SY8613-7 — Mechanical
ParameterValue
Width in modular units4
Width72 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Fastening / mounting methodQuick assembly system
Mounting positionany
Combined terminal, topYes
Combined terminal, bottomYes
Tightening torque, max.75 °C
Tightening torque, min.-40 °C
SealableYes
5SY8613-7 — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes
Influence of ambient temperature (derating)max. 95% to 55°C, max. 55% to 70°C, max. 35% to 75°C

Product details

Breaking capacity and derating

At DC per IEC 60947-2 the breaker is rated 15 kA; under UL 1077 / CSA C22.2 No.235 it carries 5 kA. Temperature derating is published: 13 A at 45 °C, 12.68 A at 50 °C, 12.34 A at 55 °C. The surrounding humidity influence is also specified — max 95% RH up to 55 °C, tapering to 35% RH at 75 °C — so the breaker is usable in unconditioned enclosures as long as the ambient profile is checked against the curve.

Rated IP20 with connected conductors (finger-safe when installed in a panel). Vibration resistance per IEC 60068-2-6: ±1 mm at 5–25 Hz, 50 m/s² at 25–150 Hz. Halogen-free and silicon-free construction, sealable, with touch protection and combined top/bottom terminals. Neutral conductor switching is integrated.

Frequently asked questions

How do I get pricing and availability for 5SY8613-7?

The 5SY8613-7 is sourced to order against an RFQ through independent distribution. Submit a request for quote; availability and current pricing are confirmed at quote time.

What is the closest functional second-source for 5SY8613-7?

The 5SY4140-7 is a peer from the same SENTRON family, but it is a different pole/current variant. The 5SY8613-7 is a 4-pole C-curve breaker; the 5SY4140-7 is a 4-pole B-curve unit. They share the same 4-module DIN footprint and 400 V AC rating, so the 5SY4140-7 will physically fit the same panel position, but the tripping curve differs — verify coordination before substituting.