Skip to main content
Delta VFD022CB23A-20 — AC Drive (VFD) 240V

Delta VFD022CB23A-20 VFD, 2.2 kW, 230V 3-Phase, IP20

MPNVFD022CB23A-20

Delta C200 Series VFD022CB23A-20 economy vector control drive, 3 HP / 2.2 kW, 230 V three-phase, IP20 wall mount, 16 A input.

$404.00Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

VFD022CB23A-20 — Mechanical
ParameterValue
Weight1.5 Kg
VFD022CB23A-20 — Other specifications
ParameterValue
VersionA=Wall mount
C200 seriesCB
Series nameVFD = Variable Frequency Drive
Product typeEconomy Vector Control Drive C200 Series
IP protection20: IP20/UL Open Type
Input current16
Input voltage23: 230 V 3-PHASE
Control method1: V/F, 2: SVC, 3: VF+PG, 4: FOC+PG
Torque limit max.200% torque current
Applicable motor capacity022:3 HP(2.2 kW)
Max. output frequencynormal duty: 0.00~600.00Hz; Heavy duty: 0.00 ~ 300.00 Hz

Product details

What's in the box and where it bolts up

The VFD022CB23A-20: Enclosure rating is IP20 / UL Open Type, which keeps the chassis out of washdown zones and confines the install to a clean control panel or a wall-mounted cubicle with filtered airflow.

Ratings that decide the fit

The 16 A input current figure on a 230 V three-phase rail is the sizing number for the feeder, breaker, and reactor upstream of the drive — wire it for continuous duty, not the motor FLA alone. The drive applies across the C200 control set: V/F, sensorless vector (SVC), V/F with encoder feedback, and field-oriented control with PG, so the same unit covers fan/pump V/F duty and closed-loop vector work without a firmware swap. Torque limit caps at 200% of rated current, which is the headroom figure for high-inertia starts, conveyors under shock load, and mixers that stall briefly before breaking free. Maximum output frequency reaches 600.00 Hz in normal duty and 300.00 Hz in heavy duty, so high-speed spindle and blower applications stay inside the drive envelope without an external frequency multiplier.

Where it sits in the C200 line

Inside the same 230 V three-phase C200 wall-mount family, the 2 HP (1.5 kW) sibling drops to a 12 A input current and the 5 HP (3.7 kW) sibling steps up to 20 A — the 16 A figure on VFD022CB23A-20 lands cleanly between them for a 3 HP load. The 460 V cousin sits at 4.0 kW on a 15.5 A input, identical footprint and chassis, and only the input voltage rail changes.

Frequently asked questions

What does VFD022CB23A-20 weigh on the AC Drive 240V line?

The unit weighs 1.5 Kg net, with a 3 Kg shipping weight on the carton — light enough for a single-technician wall mount in the field.

Will VFD022CB23A-20 drop into a panel that was specified around VFD015CB23A-20 without rewiring?

Mechanically yes — both share the same 1.5 Kg C200 wall-mount chassis in the A version. Electrically no — VFD022CB23A-20 draws 16 A input against the 12 A figure on VFD015CB23A-20, so the feeder, breaker, and any line reactor must be re-rated for the 3 HP load before the swap.

MPN
VFD022CB23A-20