Delta C2000 drive sized for 5.5 kW normal duty or 4.0 kW heavy duty
The Delta VFD055C43A is a C2000-series AC drive rated for 460 V three-phase input. It delivers 12 A output in normal duty (5.5 kW / 7.5 HP) and 11 A in heavy duty (4.0 kW / 5 HP).
Two duty ratings, one drive — choose by load profile
Normal duty: 12 A continuous, 5.5 kW, max output frequency 599.0 Hz, carrier frequency 2–15 kHz (default 8 kHz). Heavy duty: 11 A continuous, 4.0 kW, max output frequency 300.0 Hz, carrier frequency 2–6 kHz (default 2 kHz). The lower carrier ceiling on heavy duty reduces switching losses under sustained motor load — expect audible noise at 2 kHz on constant-torque applications. The normal-duty profile supports higher-speed spindles (up to 599 Hz) and quieter operation at the default 8 kHz carrier.