Capabilities at a glance
The AJ65SBTB2N-16S: Each of the 16 outputs handles 0.6 A continuous, 4.8 A per common, with a maximum inrush of 25 A for 10 ms. Rated for AC loads 100–240 V, 50/60 Hz. The on-state voltage drop is ≤1.5 Vrms at 0.6 A. Those numbers fit solenoid valves, contactor coils, or indicator lights – any AC load that stays under the 0.6 A ceiling. Isolation is photocoupler, response time 1 ms or less off→on, 1 ms + 0.5 cycles on→off.