Skip to main content
Mitsubishi Electric FR-E840-0095-4-60 — AC Drive (VFD) 480V

Mitsubishi FR-E840-0095-4-60 AC Drive, 400 V Class, 9.5 A ND

MPNFR-E840-0095-4-60

Mitsubishi Electric FR-E800 series inverter, FR-E840-0095-4-60, 400 V class, 9.5 A ND rated current, three-phase input, conformal coated circuit board, safety stop signal source logic fixed.

$489.00Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

FR-E840-0095-4-60 — Specifications
ParameterValue
4400 V class
-4Monitoring/protocol specifications : Voltage (terminal AM)Rated frequency (initial setting) : 50 HzInput signal (initial status) : Source logicSafety stop signal : Source logic (fixed)
-60Circuit board coating : With coatingPlated conductor : Without plated conductors
0095Inverter ND rated current (A)
NoneThree-phase input
Weight1.8 Kg
Product typeInverter FR-E800
Plated conductorWithout plated conductors
Safety stop signalSource logic (fixed)
Circuit board coatingWith coating
Input signal (initial status)Source logic
Rated frequency (initial setting)50 Hz
Monitoring (protocol specifications)Voltage (terminal AM)

Product details

400 V class drive with 9.5 A ND continuous rating

The FR-E840-0095-4-60 is a Mitsubishi Electric FR-E800 series inverter rated for 400 V class three-phase input — the 0095 suffix indicates a normal-duty (ND) continuous output current of 9.5 A. That current rating is the one to size the motor and cable against; the drive will deliver that current continuously without tripping the thermal model. Out of the box the initial frequency setting is 50 Hz, and the input signal logic defaults to source logic (sinking). The safety stop signal is also fixed to source logic — a detail to note when wiring the safety relay or PLC output, because a sink-logic safety device needs an interface converter.

Conformal coating and safety stop

The circuit board carries conformal coating — this is the version for environments with condensation, light chemical splash, or conductive dust. If the panel location is clean and dry, the standard uncoated variant may be sufficient; for food processing, dairy, or humid compressor rooms, this -60 suffix is the right call. The safety stop signal is fixed to source logic — that means the safety input expects a 24 VDC signal from the safety relay or gate, not a pull-down. Wire the safety loop accordingly; a sink-logic safety output will not drive this input without a level shifter.

Active production and lead time

Sourced through independent distribution and quoted to order against the BOM quantity.

Frequently asked questions

What is the ND rated current of FR-E840-0095-4-60?

The normal-duty (ND) rated current is 9.5 A. This is the continuous output current the drive can deliver without exceeding its thermal rating.

MPN
FR-E840-0095-4-60