FX1N-40MR-D key specifications
ParameterValue
10T200 to T245 46 points (0.01 to 327.67 seconds)
Output type (format)Relay output
1 ms integration type (Capacitor keep)T246 to T249 4 points (0.001 to 32.767 seconds) * Note on Keep Area Keep area and non-keep area are fixed. (Parameter can not be changed.) Large capacity condenser (built-in) will be fully charged at 30 minutes of energization time and hold the present value for 10 days. If the voltage of the large capacity capacitor decreases, the state of the capacitor keeping device may not be held correctly. Please initialize the capacitor keep device when using for the first time after purchasing the FX1N series sequencer or after using it for a long time not to turn on the power supply. Before resuming operation, please set the device and current time required for driving.
100 ms integration type (Capacitor keep)T250 to T255 6 points (0.1 to 3,276.7 seconds) * Note on Keep Area Keep area and non-keep area are fixed. (Parameter can not be changed.) Large capacity condenser (built-in) will be fully charged at 30 minutes of energization time and hold the present value for 10 days. If the voltage of the large capacity capacitor decreases, the state of the capacitor keeping device may not be held correctly. Please initialize the capacitor keep device when using for the first time after purchasing the FX1N series sequencer or after using it for a long time not to turn on the power supply. Before resuming operation, please set the device and current time required for driving.
Voltage12 to 24 VDC
Withstand voltageWhen performing the withstand voltage test, make the voltage between each terminal and the ground terminal of the basic unit as follows. Between power supply terminal (DC power supply) and earth terminal: 500 VAC for 1 minute Between output terminal (relay) and earth terminal: AC 1.5 kV 1 min
Input signal voltageDC 24 V ± 10%
Voltage tolerance rangeDC 10.2 to 28.8 V
Inrush currentUp to 25 A 1 ms or less / 24 VDC, 22 A maximum 0.2 ms or less / DC 12 V
Input OFF sensitivity current1.5 mA or less
Input signal current x000 to x0077 mA / 24 VDC
Input ON sensitivity current x000 to x0074.5 mA or more

All specifications

FX1N-40MR-D additional specifications
ParameterValue
Power consumptionIncludes 18 W input current (7 mA or 5 mA per point).
Power supply fuse125 V 3.15 A
External power supplyAC 250 V DC 30 V or less
Allowable momentary power outage timeOperation continues with an instantaneous blackout of 5 ms or less.
Frequency57 to 150 Hz : Acceleration: 9.8 m / s 2 X, Y, Z 10 times in each direction (80 minutes in total) The criteria are based on IEC 61131-2
Direct installation frequency10 to 57 Hz : One amplitude: 0.075 mm X, Y, Z 10 times in each direction (80 minutes in total) The criteria are based on IEC 61131-2
Anti-vibration when DIN rail is installed frequency10 to 57 Hz : One amplitude: 0.035 mm X, Y, Z 10 times in each direction (80 minutes in total) The criteria are based on IEC 61131-2
1 phase 1 count input[C235, C236] Up to 2 points: Up to 60 kHz High speed comparison When using SET / RESET: 30 kHz [C237 to C245] Up to 4 points: Up to 10 kHz High speed comparison When using SET / RESET: 10 kHz Processed by high- The sum of the frequencies to be summed (2-phase counter adds twice the input frequency), the maximum is 60 kHz. High Speed ??Comparison When using SET / RESET, 30 kHz is the maximum for the sum of the frequencies processed by the sequencer with the high-speed counter and pulse density instruction (2-phase counter adds twice the input frequency).
1 phase 2 count input[C246] Maximum 1 point: Up to 60 kHz High speed comparison When using SET / RESET: 30 kHz [C247 to C250] Up to 2 points: Up to 10 kHz High speed comparison When using SET / RESET: 10 kHz Frequency processed by the sequencer with high- (2-phase counter adds twice the input frequency), the maximum is 60 kHz. High Speed ??Comparison When using SET / RESET, 30 kHz is the maximum for the sum of the frequencies processed by the sequencer with the high-speed counter and pulse density instruction (2-phase counter adds twice the input frequency).
2 phase 2 count input[C251] Maximum 1 point: Up to 30 kHz High speed comparison When using SET / RESET: 15 kHz [C252 to C255] Up to 2 points: Up to 5 kHz High speed comparison When using SET / RESET: 5 kHz Frequency processed by the sequencer with high- (2-phase counter adds twice the input frequency), the maximum is 60 kHz. High Speed ??Comparison When using SET / RESET, 30 kHz is the maximum for the sum of the frequencies processed by the sequencer with the high-speed counter and pulse density instruction (2-phase counter adds twice the input frequency).
Input connection shapeRemovable terminal block (M3 screw)
Output connection shapeTerminal block (M3 screw)
Input response timeApproximately 10 ms X000 to X007 have a built-in digital filter and can be changed in 1 ms increments to 0 to 15 ms by D8020. When 0 is specified, X000, X001 is 10 μs, and X002 to X007 is 50 μs.
Response time OFF → ONAbout 10 ms
Operating temperature0 to 55 ° C. ... Operating, -20 to 70 ° C....when saved
Use altitudeIt can not be used under an environment pressurized to 2,000 m or less under atmospheric pressure. It may break down.
Relative humidity35 to 85% RH (noncondensing)...at operation
Shipping weight1.7 Kg
OtherTwo internal analog volume can be used as analog timer VR 1: D 8030, VR 2: D 8031 ??2 points (0 to 255)
GroundClass D grounding (grounding resistance: 100 Ω or less)Grounding must be dedicated ground or common ground.
Nesting[For master control] N 0 to N 7 8 points (for MC command)
ON → OFFAbout 10 ms
Total score128 points or less (when adding together)
Input formatsink
ManufacturerMitsubishi Electric
Minimum loadDC 5 V 2 mA (reference value)
Output relayY000 to Y177 128 points (octal number) When added and used
X010 or later3.5 mA or more
Inductive load80VA
Noise immunityNoise voltage with 1,000 Vp-p, noise width 1 μs, rising 1 ns, with noise si
Use atmosphereThere is no corrosive property, flammable gas, conductive dust (dust) is not serious
Hexadecimal16 bits: 0 to FFFF 32 bits: 0 to FFFFFFFF
Input interruptI00□ ~ I50□ 6 points
Special purposeM8000 to M8255 256 points
32 bit up / downC200 to C219 20 points (-2, 147, 483, 648 to +2, 147, 483, 647 counts)
For 16 bit indexV 0 to V 7, Z 0 to Z 7 16 points
Counter 16 bit upC 0 to C 15 16 points (0 to 32,767 counts)
Impact resistance147 m / s 2 , working time 11 ms, criterion for judgment three times in X, Y, Z directions by sine half-wave pulse is according to IEC 61131-2
16 bit special useD 8000 to D 8255 256 points
Circuit insulationMechanical insulation
High speed counter[32-bit high-speed up / down (EEPROM Keep)] C235 ~ C255 1 phase: 60 kHz, 10 kHz 2 phase: 30 kHz, 5 kHz there is a limit to the number and input frequency that can be used according to the conditions used. ※ Note on Keep Area Keep area and non-keep area are fixed. (Parameter can not be changed.) In order to reliably keep to EEPROM, it is necessary for the sequencer to be energized for at least 5 consecutive minutes.
Keep (EEPROM keep)S10 to S127 118 points ※ Note on Keep Area Keep area and non-keep area are fixed. (Parameter can not be changed.) In order to reliably keep to EEPROM, it is necessary for the sequencer to be energized for at least 5 consecutive minutes.
Estimated lead timeUsually ships in 1 - 10 working days.
Input signal formatNo-voltage contact input NPN open collector transistor
Protection functionWith password protection function (by keyword function)
File registerD1000 to D7999 Up to 7000 points (It can be set to program area (EEPROM) as file register in units of 500 points from D1000 according to parameters)
Programming languageRelay symbol method + step ladder method (SFC expressible)
Insulation resistanceWhen conducting the insulation resistance test, perform the following voltage between each terminal and the ground terminal of the basic unit. Between power supply terminal (DC power supply) and earth terminal: 500 VDC DC insulation resistance meter 5 MΩ or more Output terminal (relay) and earth terminal: 500 VDC with insulation resistance meter 5 MΩ or more
Keep (capacitor keep)S128 to S999 872 points ※ Note on keeping area Keep area and nonkeeping area are fixed. (Parameter can not be changed.) Large capacity condenser (built-in) will be fully charged at 30 minutes of energization time and hold the present value for 10 days. If the voltage of the large capacity capacitor decreases, the state of the capacitor keeping device may not be held correctly. Please initialize the capacitor keep device when using for the first time after purchasing the FX1N series sequencer or after using it for a long time not to turn on the power supply. Before resuming operation, please set the device and current time required for driving.
Number of input points24 points
16 bit up (EEPROM keep)C16 to C31 16 points (0 to 32,767 counts) * Note on keep area Keep area and non-keep area are fixed. (Parameter can not be changed.) In order to reliably keep to EEPROM, it is necessary for the sequencer to be energized for at least 5 consecutive minutes.
Application instruction3.7 to several 100 μs / instructions
Input operation displayLED ON when input is ON
Number of output points16 points
Timer (on-delay) 100T0 to T199 200 points (0.1 to 3,276.7 seconds)
Input circuit insulationPhotocoupler insulation
Arithmetic control methodStored program iterative calculation method with interrupt instruction
Write function during RUNYes (program changeable during sequencer RUN)
16 bit up (Capacitor keep)C32 to C199 168 points (0 to 32,767 counts) * Note on keeping area Keep area and nonkeeping area are fixed. (Parameter can not be changed.) Large capacity condenser (built-in) will be fully charged at 30 minutes of energization time and hold the present value for 10 days. If the voltage of the large capacity capacitor decreases, the state of the capacitor keeping device may not be held correctly. Please initialize the capacitor keep device when using for the first time after purchasing the FX1N series sequencer or after using it for a long time not to turn on the power supply. Before resuming operation, please set the device and current time required for driving.
Maximum load resistive load2A or less / per output 8 A or less / per COM terminal
Output operation indicationLED lit when relay coil is energized
Constant decimal number16 bits: -32,768 to + 32,767 32 bits: -2, 147, 483, 648 to +2, 147, 483, 647
Input impedance x000 to x0073.3 kΩ
For 16-bit keep (EEPROM keep)D128 to D255 128 points ※ Note on the keep area Keep area and non-keep area are fixed. (Parameter can not be changed.) In order to reliably keep to EEPROM, it is necessary for the sequencer to be energized for at least 5 consecutive minutes.
Input (output control method)Batch processing method (when END instruction is executed), I / O refresh command, with pulse catch function
Pointer JUMP, for CALL branchP0 to P127 128 points (for CJ instruction, CALL instruction, P63 for END jump)
Memory cassette (memory board)FX1N-EEPROM-8L (8000 step EEPROM)
Real time clock clock functionBuilt-in 1980 to 2079 (with leap year correction) 2-digit / 4-digit year AD changeable, monthly difference ± 45 seconds (25 ° C) ※ Note on clock function The current time of the built- It is backed up with. The large capacity condenser (built-in) is fully charged at the energization time of 30 minutes and holds the present value for 10 days. Also, you can hold it with a battery by using an optional battery.
Device i (O relay input relay)X000 to X177 128 points (octal number) When added and used
Auxiliary relay for general useM 0 to M 383 384 points
For 16-bit keep (capacitor keep)D256 to D7999 7744 points ※ Note on Keep Area Keep area and non-keep area are fixed. (Parameter can not be changed.) Large capacity condenser (built-in) will be fully charged at 30 minutes of energization time and hold the present value for 10 days. If the voltage of the large capacity capacitor decreases, the state of the capacitor keeping device may not be held correctly. Please initialize the capacitor keep device when using for the first time after purchasing the FX1N series sequencer or after using it for a long time not to turn on the power supply. Before resuming operation, please set the device and current time required for driving.
32 bit up / down (Capacitor keep)C220 to C234 15 points (-2, 147, 483, 648 to +2, 147, 483, 647 counts) * Note on Keep Area Keep area and nonkeeping area are fixed. (Parameter can not be changed.) Large capacity condenser (built-in) will be fully charged at 30 minutes of energization time and hold the present value for 10 days. If the voltage of the large capacity capacitor decreases, the state of the capacitor keeping device may not be held correctly. Please initialize the capacitor keep device when using for the first time after purchasing the FX1N series sequencer or after using it for a long time not to turn on the power supply. Before resuming operation, please set the device and current time required for driving.
Internal memory capacity (format)8000 steps EEPROM (memory backup not required)
State initial state (EEPROM keep)S0 to S9 10 points ※ Note on keeping area Keep area and nonkeeping area are fixed. (Parameter can not be changed.) In order to reliably keep to EEPROM, it is necessary for the sequencer to be energized for at least 5 consecutive minutes.
Program memory maximum memory capacity8000 step comments, maximum 8000 steps including file register
Types of instructions basic instruction. Sequence instruction: 27 pieces . Step ladder command: 2 pieces
Number of remote i (O points (CC - link))128 points or less including real I / O
Arithmetic processing speed basic instruction0.55 to 0.7 μs / instructions
Number of input (output points number of input points)128 points or less (at the time of addition and extension use) However, the input / output total is 128 points or less
Data register (32 bits in pair use) for 16-bit general purposeD0 to D127 128 points
MPN