Specifications
| Parameter | Value |
|---|---|
| Withstand voltage | Between external terminals and ground terminal of PLC main unit: AC 500 V for 1 minute |
| Power-supply voltage | DC 5 V 120 mA (Internal power supply from PLC) |
| Input signal voltage START, DOG, x0, x1 | DC 24 V ± 10% |
| Rated load voltage pulse output unit (FP (RP)) | DC 5 V to 24 V (power supplied from the VIN terminal) |
| Maximum voltage drop during ON clear signal | 1.5V or less |
| Input signal current START, DOG, x0, x1 | 6.5 mA ± 1 mA |
| Leakage current when OFF clear signal | 0.1 mA or less |
| Maximum load current pulse output unit (FP (RP)) | 25 mA or less |
| VIN consumption current pulse output unit (FP (RP)) | At 24 VDC: 70 mA at 5 VDC : 100 mA |
| Absolute position detection (ABS current value reading) | Use sequencer's ABS command |
| Frequency | 57 to 150 Hz : Acceleration: 9.8 m / s 2 10 times in X, Y, Z directions (80 minutes in total) |
| Output frequency | 1 MHz |
All specifications+38 ▾
| Parameter | Value |
|---|---|
| Maximum frequency | 1 MHz |
| Direct installation frequency | 10 to 57 Hz : One amplitude: 0.075 mm X, Y, Z 10 times in each direction (80 minutes in total) |
| Anti-vibration when DIN rail is installed frequency | 10 to 57 Hz : One amplitude: 0.035 mm X, Y, Z 10 times in each direction (80 minutes in total) |
| Operating temperature | 0 to 55 ° C. ... Operating, -25 to 75 ° C. ..... Save |
| Use altitude | Can not be used in an environment pressurized to 2000 m or less under atmospheric pressure. It may break down. |
| Relative humidity | 5 to 95% RH (noncondensing).... in operation |
| Shipping weight | 1.2 Kg |
| Mass | 0.2 Kg |
| PG 0 | Pulse width 50 μs or more |
| Φ a, φ b | 2 phase pulse 30 kHz or less (Duty 50%) |
| Control unit | pulse, μm, 10 -4 inch, mdeg |
| Manufacturer | Mitsubishi Electric |
| Control input | Control input: 3 points (START, DOG, PG 0) Interrupt input: 2 points (X0, X1) 2 phase pulser input: 1 point (φA, φB) |
| Position data | 1 point (set with sequence program) 200 point (table) can be set when table positioning operation is performed. |
| Noise immunity | Noise voltage with 1,000 Vp-p, noise width 1 μs, rising 1 ns, with noise si |
| Use atmosphere | There is no corrosive property, flammable gas, conductive dust (dust) is not serious |
| Impact resistance | 147 m / s 2 , working time 11 ms, three times in X, Y, Z directions with a sine half-wave pulse |
| Positioning range | -2, 147, 483, 648 to +2, 147, 483, 647 pulse -2, 147, 483, 648 to +2, 147, 483, 647 [X (position data magnification) μm] -2, 147, 483, 648 to +2, 147, 483, 647 [X (position data magnification) X 10 -4 inch] -2, 147, 483, 648 to +2, 147, 483, 647 [X (position data magnification) mdeg] The position data magnification can be set to X 1, X 10, X 10 2, or X 10 3 in the parameter. It can be set in the range of -2, 147, 483, 648 to +2, 147, 483, 647 in terms of pulse conversion value. |
| Pulse output form | Pulse train + direction, forward rotation / reverse rotation pulse train |
| Circuit insulation | Photocoupler insulation |
| Clear signal | 20 mA or less |
| Estimated lead time | 1 - 10 Working Days |
| Pulse output method | Differential line driver system |
| Programming language | BFM can be specified directly by sequence program (FROM / TO instruction, application instruction operand) |
| Application sequencer | FX2N, FX3U, FX2NC, FX3UCFX2NC - CNV - IF is required for connection to FX2NC. To connect to FX3UC, FX2NC - CNV - IF or FX3UC - 1PS - 5V is required. |
| Insulation resistance | Between the external terminals collectively and the ground terminal of the programmable controller main body: 500 MV DC insulation resistance meter 5 MΩ or more |
| Number of control axes | Independent single axis |
| Input operation display | LED ON when input is ON |
| Number of output points | 3 points (FP, RP, CLR) |
| Output operation indication | LED on when output is ON |
| Number of occupied i (O points) | Sequencer input / output 8 points occupation (It can count either input or output) |
| Acceleration (deceleration processing) | Automatic trapezoidal acceleration / deceleration, approximate S-shaped acceleration / deceleration |
| Input capture speed START, DOG, x0, x1 | 0.1 ms or less (DOG is 1.0 ms or less) |
| Input signal format START, DOG, x0, x1 | Contact or open collector transistor |
| Input ON sensitivity START, DOG, x0, x1 | 4.5 mA or more |
| Output form pulse output unit (FP (RP)) | You can select forward rotation (FP) / reverse rotation (RP) or pulse (PLS) / direction (DIR). |
| Input OFF sensitivity START, DOG, x0, x1 | 1.5 mA or less |
| Output method pulse output unit (FP (RP)) | Differential line driver output |