FX2N-2LC - Mitsubishi Electric
MPNFX2N-2LC
End of Life
Temperature adjustment block
$169.00Ref. price · indicative, final on quote
StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jun 2026
Specifications
Specifications
| Parameter | Value |
|---|---|
| Frequency | 57 to 150 HzAcceleration: 9.8 m / s 2 X, Y, Z each 10 times (total 80 minutes each) |
| Operation mode0 | Measured value monitor 1: Measured value monitor + temperature alarm 2: Measured value monitor + temperature alarm + control (selected by buffer memory) |
| Direct mountingFrequency | 10 to 57 HzSingle amplitude: 0.075 mm X, Y, Z each direction 10 times (total 80 minutes each) |
| Noise resistantNoise voltage | 1,000 Vp-p, noise width: 1 μs, rise time: 1 ns, period: 30 to 100 Hz noise simulator |
| memoryBuilt-in EEPROM (number of rewrites | 100,000 times) |
| groundType d grounding (Grounding resistance | 100 Ω or less) < Do not connect to a common ground with a high-power system> Connect a dedicated ground or shared ground. |
| Vibration resistanceWhen mounting DIN railFrequency | 10 to 57 HzSingle amplitude: 0.035 mm X, Y, Z each direction 10 times (total 80 minutes each) |
| Measurement accuracyambient temperature 23 ° c ± 5 ° | Input range ± 0.3% ± 1 digit Ambient temperature 0 ° C to 55 ° C: Input range ± 0.7% ± 1 digit However, B input 0 to 399 ° C (0 to 799 ° F) and PLII , 0 to 32 ° F of WRe5-26 input is out of guaranteed accuracy range |
| Withstand voltageBetween analog input terminal and ground terminal | AC500V 1 minute |
| Insulation resistanceBetween analog input terminal and ground terminal | 5 MΩ or more with DC 500 V insulation resistance tester |
| Current detector (CT) input (heater current measurement value)When using CTL-12 | 0.0 to 100.0 A When using CTL-6: 0.0 to 30.0 A |
MPN