Specifications

FX3U-4AD-PT-ADP key specifications
ParameterValue
Withstand voltageBetween all terminals and ground terminal: 500 VAC for 1 minute
Power supplyDC 5 V 15 mA (internal power supply from the sequencer) DC 24 V + 20% -15% 50 mA (external power supply)
Frequency57 to 150 Hz : Acceleration: 9.8 m / s 2 10 times in X, Y, Z directions (80 minutes in total)
Direct installation frequency10 to 57 Hz : One amplitude: 0.075 mm X, Y, Z 10 times in each direction (80 minutes in total)
Anti-vibration when DIN rail is installed frequency10 to 57 Hz : One amplitude: 0.035 mm X, Y, Z 10 times in each direction (80 minutes in total)
Operating temperature0 to 55 ° C. ... Operating -25 to 75 ° C. ..... Save
Rated temperature range-50 ° C to + 250 ° C (-58 ° F to + 482 ° F)
Use altitudeCan not be used in an environment pressurized to 2000 m or less under atmospheric pressure. It may break down.
Relative humidity5 to 95% RH (noncondensing).... in operation
Shipping weight1 Kg
Mass0.1 Kg
GroundClass D grounding (grounding resistance: 100 Ω or less)Grounding should be dedicated ground or common ground.

All specifications

FX3U-4AD-PT-ADP additional specifications
ParameterValue
Resolution0.1 ° C (0.18 ° F)
ManufacturerMitsubishi Electric
Control methodDepending on the sequence program
Digital output-500 to + 2500 (-580 to + 4820 ) Within parentheses, the digital value at Fahrenheit setting
Noise immunityNoise voltage with 1,000 Vp-p, noise width 1 μs, rising 1 ns, with noise si
Use atmosphereThere is no corrosive property, flammable gas, conductive dust (dust) is not serious
Overall accuracyAmbient temperature 25 ° C ± 5 ° C: ± 0.5% with full scale Ambient temperature 0 ° C to 55 ° C: ± 1.0% with full scale
Impact resistance147 m / s 2 , working time 11 ms, three times in X, Y, Z directions with a sine half-wave pulse
Insulation method. Isolation between analog input part and sequencer by photo coupler . Insulation between analog input part and power supply by DC / DC converter . No isolation between each channel
Estimated lead time1 - 10 Working Days
Application sequencerFX3S, FX3G, FX3U, FX3GC, FX3UC (FX3UC - 32MT - LT is Ver.1.30 or later) FX3S - CNV - ADP is required for connection to FX3S. For connection to FX 3 G, FX 3 G - CNV - ADP is required. To connect to FX3U and FX3UC - 32MT - LT (-2), a function expansion board is required.
Insulation resistanceBetween all terminals and ground terminal: 500 MV DC 500 MΩ or more with an insulation resistance meter
Number of input channels4 channels
FX3S / FX3G / FX3GC sequencer250 μs (Data update every calculation cycle)
Number of occupied i (O points)0 point (It does not relate to the maximum input / output point number of the sequencer)
Conversion speed FX3U / FX3UC PLC200 μs (Data update every calculation cycle)
Temperature sensor . temperature control input signalPlatinum resistance temperature detector 3 wire type Pt 100 JIS C 1604 - 1997