Skip to main content
Mitsubishi Electric QX41Y41P — Digital Output Modules

Mitsubishi QX41Y41P PLC I/O Module

MPNQX41Y41P

Mitsubishi MELSEC-Q Series Input/Output Unit

$394.00 – $937.93Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

QX41Y41P key specifications
ParameterValue
Input common type32 points 1 common
Withstand voltageAC 560 Vrms / 3 cycles (altitude 2000 m)
Rated load voltageDC 12 to 24 V (+ 20 / -15%)
Rated input voltageDC 24 V (+ 20 / -15%, ripple ratio within 5%)
ON voltage (ON current)19 V or more / 3 mA or more
OFF voltage (OFF current)11 V or less / 1.7 mA or less
External power supply voltageDC 12 to 24 V (+ 20 / -15%) (ripple ratio within 5%)
Maximum voltage drop during ONDC 0.1 V (TYP.) 0.1 A, DC 0.2 V (MAX.) 0.1 A
CurrentMaximum 15mA / 1 common (24 VDC, all points ON)
Rated input currentAbout 4 mA
Maximum load current0.1 A / 1 point, 2 A / 1 common
Leakage current at OFF0.1 mA or less

All specifications

QX41Y41P additional specifications
ParameterValue
Maximum inrush current0.7 A less than 10 ms
DC 5 v internal current consumption130 mA (TYP. All points ON)
Applicable connectorA6CON1, A6CON2, A6CON3, A6CON4 (sold separately)
External wiring connection method40 pin connector X 2
Input response time OFF → ON1 ms / 5 ms / 10 ms / 20 ms / 70 ms or less
Output response time OFF → ON1ms or less
Surge suppressorZener diode
Depth90 mm
Width27.4 mm
Shipping weight1.2 Kg
External dimensions height98 mm
Mass0.20 Kg
ON → OFF1 ms or less (rated load, resistance load)
Input formatDC input (plus common type)
ManufacturerMitsubishi Electric
Output formatTransistor output (sink type)
Input resistanceAbout 5.6 kΩ
Protection gradeIP2X
Insulation methodPhotocoupler isolation
Estimated lead timeUsually ships in 1 - 10 working days.
Operation indicationON indication (LED) SW display with 32 switches
Output common method32 points 1 common
Insulation resistance10 MΩ or more with an insulation resistance meter
Number of input points32 points
Number of output points32 points
Overload protection functionOvercurrent detection, overload protection limit current: 1 to 3A / 1 point operation in 1 point
Number of occupied i (O points)64 points (I / O assignment: 64 input / output mixing points)
Protection function overheat protection functionOperate in units of 1 point
MPN